The 7/8" diameter hole for the electrical conduit can
be located in two different locations in the top cap
depending upon which furnace model that the vent
adapter is being applied. The two locations are
labeled I and II on the Vent Adapter Kit Conduit
Placement Template included with the kit.

Location I is for furnaces with A (14.5"), C (21.00" and
D (24.50") width cabinets. Location II is for furnaces
with B (17.50") width cabinets.

 3 − Position the vent adapter assembly on the furnace

flue transition as shown in figure 4 (location II).

FIGURE 4

TYPE B

DOUBLE

WALLED

VENT PIPE

VENT ADAPTER

ASSEMBLY

CONDUIT

VENT ADAPTER ASSEMBLY INSTALLATION

(B

Size Cabinet Shown)

 4 − Remove the locknut from the vent adapter assembly

conduit. Route the two wires through the 7/8" hole in the
furnace top cap. Use the locknut to secure the conduit
to the furnace top cap.

 5 − Use three field−provided, self−drilling sheet metal

screws to firmly secure the vent adapter assembly to
the round collar of the unit flue transition. Drive one
self−drilling screw through the front and one through
each side of the vent adapter assembly and collar.

WARNING

Asphyxiation hazard. The vent adapter assembly
must be securely attached to the furnace flue tran-
sition and the vent pipe at all times.

 6 − The vent adapter assembly includes a blocked vent

switch which must be wired into the furnace
combustion air proving pressure switch as shown in
figure 5. This manually reset switch interrupts unit
operation when the vent is blocked. The switch must
not be reset until vent blockage is cleared.
 a − Remove one of the purple wires from the

combustion air proving pressure switch.
Connect this wire to the switch wire with the male
1/4" quick connect terminal.

 b − Connect the switch wire with the female 1/4"

quick connect terminal to the open contact on the
combustion air proving pressure switch.

FIELD WIRING

FIGURE 5

VENT ADAPTER

ASSEMBLY

(with blocked vent

switch)

WIRE WITH 1/4"
FEMALE QUICK

CONNECT

TERMINAL

PURPLE WIRE

PURPLE WIRE

DISCONNECT

FROM PRESSURE

SWITCH

WIRE WITH 1/4"

MALE QUICK

CONNECT

TERMINAL

PRESSURE SWITCH

(Low pressure switch on

SL280UH models)

 7 − Use three field−provided self−drilling screws to secure

the double−walled B−vent to the top of the vent adapter
assembly. Drive one self−drilling screw through the
front and one through each side. Route the vent to the
masonry chimney using the shortest possible route.
If an elbow is required to route the vent connector to
the chimney, it must be installed at least 1 ft. above the
furnace vent outlet. A 2 ft. clearance before the first
elbow is preferable. See figure 6.

Содержание 92W76

Страница 1: ...ed in masonry chimney vent applications in accordance with limitations set by NFPA 54 and the International Mechanical Code The included vent tables and guidelines must be followed exactly to ensure p...

Страница 2: ...10 F 12 C Pittsburgh 1 F 17 C Salt Lake City 3 F 16 C St Louis 2 F 17 C Requirements The room temperature surrounding the furnace and vent connectors must be at least 60 F 16 C The space surrounding t...

Страница 3: ...mney and vent connector per table 3 and figure 2 when a single appliance is being vented into an interior masonry chimney Size the chimney and vent connector per tables 4 and 5 and figure 3 when using...

Страница 4: ...le Lined Masonry Chimney Serving a Single Furnace Equipped with Vent Adapter Kit and One or More Drafthood Equipped Appliances Typical Application Shown FIGURE 3 TILE LINED MASONRY CHIMNEY PERMANENTLY...

Страница 5: ...145 148 179 206 210 240 276 10 1 2 3 108 129 148 153 184 209 216 247 281 15 1 2 3 114 134 153 164 192 215 229 260 292 20 1 2 3 119 138 157 173 199 222 239 270 301 30 1 2 3 127 145 163 187 209 233 255...

Страница 6: ...sing mortar or brick must be replaced Tile liner and top seal must be in good condition If necessary make repairs All debris mortar tile fuel oil residue etc must be removed from chimney clean out Til...

Страница 7: ...to the furnace flue tran sition and the vent pipe at all times 6 The vent adapter assembly includes a blocked vent switch which must be wired into the furnace combustion air proving pressure switch a...

Страница 8: ...al setting 11 Test the furnace for proper draft and spillage a Inspect the venting system for proper size and horizontal pitch Determine that there is no blockage restriction leakage corrosion or othe...

Отзывы: