Page 27
TABLE 17
Maximum Allowable Intake or Exhaust Vent Length in Feet
NOTE - Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and Exhaust must
be same pipe size
.
Standard Termination at Elevation 0 - 4500 ft
Number
Of 90°
Elbows
Used
1-1/2” Pipe
2” Pipe
2-1/2” Pipe
3” Pipe
Model
Model
Model
Model
045 070 090 110 135 045 070 090 110 135 045 070 090 110 135 045 070 090 110 135
1
25
20
n/a n/a n/a
81
66
44 24
n/a
115 115 93 58
n/a
138 137 118 118 114
2
20
15
76 61
39
19
110 110 88 53
133 132 113 113 109
3
15
10
71
56
34 14
105 105 83 48
128
127
108 108 104
4
10
n/a
66
51
29
n/a
100 100 78 43
123
122
103 103
99
5
n/a
61
46
24
95 95 73 38
118
117
98 98
94
6
56 41
19
90 90 68 33
113
112
93 93
89
7
51 36
14
85 85 63 28
108 107 88 88
84
8
46 31
n/a
80 80 58 23
103 102 83 83
79
9
41
26
75 75 53 18
98
97
78 78
74
10
36
21
70 70 48 13
93
92
73 73
69
Standard Termination Elevation 4500 - 10,000 ft
Number
Of 90°
Elbows
Usedl
1-1/2” Pipe
2” Pipe
2-1/2” Pipe
3” Pipe
Model
Model
Model
Model
045 070 090 110 135 045 070 090 110 135 045 070 090 110 135 045 070 090 110 135
1
25
20
n/a n/a n/a
81
66
44
n/a n/a
115 115 93 58
n/a
138 137 118 118 114
2
20
15
76 61
39
110 110 88 53
133 132 113 113 109
3
15
10
71
56
34
105 105 83 48
128
127
108 108 104
4
10
n/a
66
51
29
100 100 78 43
123
122
103 103
99
5
n/a
61
46
24
95
96
73 38
118
117
98 98
94
6
56 41
19
90 90 68 33
113
112
93 93
89
7
51 36
14
85 85 63 28
108 107 88 88
84
8
46 31
n/a
80 80 58 23
103 102 83 83
79
9
41
26
75 75 53 18
98
97
78 78
74
10
36
21
70 70 48 13
93
92
73 73
69
See concentric terminations next page.
Содержание 5625717