Page 2
SPECIFICATIONS
Gas
Heating
Performance
Model No. EL296UH045XE36B EL296UH070XE36B EL296UH090XE48C
AHRI Ref. No.
5625717
5625718
5625719
1
AFUE
96%
96%
96%
High
Fire
Input - Btuh
44,000
66,000
88,000
Output - Btuh
43,000
64,000
84,000
Temperature rise range - °F
30-60
35-65
40-70
Gas Manifold Pressure (in. w.g.)
Nat. Gas / LPG/Propane
3.5 / 10.0
3.5 / 10.0
3.5 / 10.0
Low
Fire
Input - Btuh
29,000
43,000
57,000
Output - Btuh
28,000
42,000
55,000
Temperature rise range - °F
20 - 50
25 - 55
30 - 60
Gas Manifold Pressure (in. w.g.) Nat. Gas / LPG/Propane
1.7 / 4.5
1.7 / 4.5
1.7 / 4.5
High static - in. w.g.
0.5
0.5
0.5
Connections
in.
Intake / Exhaust Pipe (PVC)
2 / 2
2 / 2
2 / 2
Gas pipe size IPS
1/2
1/2
1/2
Condensate Drain Trap (PVC pipe) - i.d.
3/4
3/4
3/4
with furnished 90° street elbow
3/4 slip x 3/4 Mipt
3/4 slip x 3/4 Mipt
3/4 slip x 3/4 Mipt
with field supplied (PVC coupling) - o.d.
3/4 slip x 3/4 MPT
3/4 slip x 3/4 MPT
3/4 slip x 3/4 MPT
Indoor
Blower
Wheel nominal diameter x width - in.
10 x 8
10 x 8
10 x 10
Motor Type
DC Brushless
DC Brushless
DC Brushless
Motor output - hp
1/2
1/2
3/4
Tons of add-on cooling
1.5 - 3
1.5 - 3
2.5 - 4
Air Volume Range - cfm
520 - 1345
550 - 1380
760 - 1740
Electrical Data
Voltage
120 volts - 60 hertz - 1 phase
Blower motor full load amps
6.8
6.8
8.4
Maximum overcurrent protection
15
15
15
Shipping Data
lbs. - 1 package
129
133
159
NOTE - Filters and provisions for mounting are not furnished and must be field provided.
1
Annual Fuel Utilization Efficiency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized
furnaces.
SPECIFICATIONS
Gas
Heating
Performance
Model No.
EL296UH110XE60C
EL296UH135XE60D
AHRI Ref. No.
5625720
5625721
1
AFUE
96%
96%
High
Fire
Input - Btuh
110,000
132,000
Output - Btuh
106,000
127,000
Temperature rise range - °F
40-70
45-75
Gas Manifold Pressure (in. w.g.)
Nat. Gas / LPG/Propane
3.5 / 10.0
3.5 / 10.0
Low
Fire
Input - Btuh
72,000
86,000
Output - Btuh
70,000
84,000
Temperature rise range - °F
30-60
35-65
Gas Manifold Pressure (in. w.g.) Nat. Gas / LPG/Propane
1.7 / 4.9
1.7 / 4.9
High static - in. w.g.
0.5
0.5
Connections
in.
Intake / Exhaust Pipe (PVC)
2 / 2
2 / 2
Gas pipe size IPS
1/2
1/2
Condensate Drain Trap (PVC pipe) - i.d.
3/4
3/4
with furnished 90° street elbow
3/4 slip x 3/4 Mipt
3/4 slip x 3/4 Mipt
with field supplied (PVC coupling) - o.d.
3/4 slip x 3/4 MPT
3/4 slip x 3/4 MPT
Indoor
Blower
Wheel nominal diameter x width - in.
11-1/2 x 10
11-1/2 x 10
Motor Type
DC Brushless
DC Brushless
Motor output - hp
1
1
Tons of add-on cooling
3 - 5
3.5 - 5
Air Volume Range - cfm
1055 - 2220
1260 - 2405
Electrical Data
Voltage
120 volts - 60 hertz - 1 phase
Blower motor full load amps
10.9
10.9
Maximum overcurrent protection
15
15
Shipping Data
lbs. - 1 package
174
189
NOTE - Filters and provisions for mounting are not furnished and must be field provided.
1
Annual Fuel Utilization Efficiency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized
furnaces.
Содержание 5625717
Страница 53: ...Page 53 VII Wiring and Sequence of Operation...