PRELIMINARY CHECKS
CHILLER-IOM-2004-E
28
5.
HYDRAULIC CONNECTIONS AND OPTIONS (FOR HYDROLEAN AND MWC)
Standard connections are Victaulic type for MWC and external threaded for Hydrolean, flange connections (MWC only) and filters are
options.
For the commissioning, the flow switch must be mounted on the pipe “S” for the evaporator and connected on the flow switch electrical
cable via a special connecter. And the outlet sensors must be mounted in the pocket bulbs. The flow switch cable and the outlet sensor
cables are already connected to the electrical panel and attached on the frame. The filters are mounted on the heat exchanger inlets.
1:
Condenser
2:
Evaporator
B:
Plug
DN: Diameter
E:
Water inlet
OB: Flange option
OF: Filter option
S:
Water outlet
SE: Evaporator pocket bulb
SC: Condenser pocket bulb
SD1: Flow switch
V:
Valve