TEST MODE
To test the detection coverage:
During the TEST mode, the controlled load turns ON for 5 seconds each time the
sensor detects occupancy.
1. Press and hold the ON/OFF button. After 10 seconds the lighted switch fl ashes.
The controlled load turns ON if it was not already ON. The sensor is now in
a TEST mode that lasts 5 minutes. (You can end the TEST mode sooner by
pressing the ON/OFF button for another 10 seconds).
2. Move out of the coverage area or stand very still. The controlled load turns OFF
after 5 seconds if no motion is detected.
3. Move into the coverage area. The controlled load turns ON for 5 seconds
each time the sensor detects motion. After 5 seconds expire without motion
detection, the load turns OFF. The controlled load turns ON automatically with
the next motion detection and stays ON for 5 seconds.
4. Repeat as necessary to ensure that the desired coverage areas are within
detection range.
TROUBLESHOOTING
Load will not turn ON (lighted switch is visible):
• Move in front of the sensor to automatically turn lights ON. If lights do not turn
ON, press the ON/OFF button. The lighted switch should turn OFF and the
controlled load should turn ON, if not:
• Check the light bulb.
• Make certain the circuit breaker is ON and functioning.
• Turn OFF power to the circuit then check wire connections.
• Remember that if the load is turned OFF manually, Automatic-ON is reenabled
only after no motion is detected for 5 minutes.
Light will not turn ON (lighted switch is NOT visible):
• Check the light bulb.
• Make certain that the circuit breaker is ON and functioning.
• Turn OFF power to the circuit then check wire connections.
Load will not turn OFF:
The time delay is 5 minutes (fi xed time delay).
• Make sure no motion occurs in the coverage area until the time delay expires.
• If the load does not turn OFF, call Technical Support at 888-817-0571.
• Hot air currents and heat radiant devices can cause false detection. Make sure
the sensor is at least 6 feet (2 meters) away from devices that are a signifi cant
heat source (e.g heater, heater vent, high wattage light bulb).
• Press the ON/OFF button. If the controlled load does not turn OFF, turn OFF
the power to the circuit, then check wire connections.
WARRANTY INFORMATION
Watt Stopper/Legrand warranties its products to be free of defects in materials
and workmanship for a period of fi ve (5) years. There are no obligations or
liabilities on the part of Watt Stopper/Legrand for consequential damages arising
out of, or in connection with, the use or performance of this product or other
indirect damages with respect to loss of property, revenue or profi t, or cost of
removal, installation or reinstallation.
2800 De La Cruz Boulevard, Santa Clara, CA 95050
Technical Support: 888.817.0571
www.wattstopper.com/athome
06018r2 2/2007
Please
Recycle