6

CONFIGURATION

The configuration process establishes the appropriate parameters for operation. This is done 

through the use of an LMCT-100 configuration tool. If no configuration steps are taken, the sensor 

will use its default values for setpoints.
The LMCT-100 Wireless IR Configuration Tool is a handheld tool for setup and testing of 

Wattstopper Digital Lighting Management (DLM) devices. It provides wireless access to 

occupancy and daylighting sensors for setup and parameter changes, Wattstopper Push n’ 

Learn™ (PnL) technology for load configuration, switch and dimmer assignment and operating 

parameter changes. The LMCT-100’s display shows menus and prompts to lead you through each 

process. The navigation pad provides a familiar way to navigate through the customization fields. 

The LMCT-100 allows modification of the system without requiring ladders or tools; simply with a touch of a few buttons.

Operation

The LMCT-100’s IR transceiver allows bi-directional communication between DLM devices and the LMCT-100. Simple menu screens let 

you see the current status of the system and make changes.
For systems including the LMLS-500 daylighting sensor the LMCT-100 can also set or change the daylight parameters. The LMCT-100 

can change dimming system options such as scene assignments, ramp rates and other options not available through the standard user 

interface.

Batteries

The LMCT-100 operates on three standard 1.5V AAA Alkaline  batteries or 

three rechargeable AAA NiMH batteries.

The battery status displays in the upper right corner of the display. Three bars next to BAT= 

indicates a full battery charge. A warning appears on the display when the battery level falls 

below a minimum acceptable level.
To conserve battery power, the LMCT-100 automatically shuts OFF 10 minutes after the 

last key press.

Navigation

You navigate from one  field to another using 

(up) or 

(down) arrow keys. The active 

field is indicated by flashing (alternates between yellow text on black background and black 

text on yellow background).
Once active, use the 

Select

 button to move to a menu or function within the active field.

Value fields are used to adjust parameter settings. They are shown in “less-than/greater-

than” symbols: <value>. Once active, change them using

(left) and

(right) arrow keys. 

In general the

key increments and the

key decrements a value. Selections wrap-

around if you continue to press the key beyond maximum or minimum values. Moving 

away from the value field (using 

/

 keys) overwrites the original value.

The 

 button takes you to the main menu.

The 

 button can be thought of as an undo function. It takes you back one screen. 

Changes that were in process prior to pressing the 

 key are lost.

Home Menu

The Home (or Main) menu displays after the power-up process completes. It contains 

information on the battery status and six menu choices.
Press 

/

 to locate the desired function then press 

Select

.

Select

Button

Up or Down

Button

S e n s o r   C o n fi g u r a t i o n

L o a d   C o n fi g   ( P n L )

D a y l i g h t i n g   C o n fi g

B u t t o n   C o n fi g u r a t i o n

D i m m i n g   C o n fi g u r a t i o n

  

    M o r e

=

B AT

Press Left/Right arrow

to select a value

Value Fields

Parameters

S E N D     N E X T   Z O N E       D O N E

D a y l i g h t i n g         L M L S - 5 0 0

Z o n e   1  

  D i m m ed

S e t p o i n t :

R a m p   U p:

R a m p   D o w n:
C u t   O ff Delay:

< 5 0 f c >

< 2 0 % s e c >

< 2 % s e c >

< 1 0 m i n>

Function Fields (on Home Menu)

S e n s o r   C o n fi g u r a t i o n

L o a d   C o n fi g   ( P n L )

D a y l i g h t i n g   C o n fi g

B u t t o n   C o n fi g u r a t i o n

D i m m i n g   C o n fi g u r a t i o n

  

    M o r e

=

B AT

Fig. 10: LMCT-100

Fig. 11: Battery Location

Sensor Configuration

Load Config (PnL)

Daylighting Config

Button Configuration

Dimming Configuration

               More

Home/
Main Menu

Up

Select

Down

Right/Next

Left

Back

Power

On/Off

IR Window

BAT=

Fig. 12: LMCT-100 Controls

Содержание Wattstopper LMLS-500

Страница 1: ...three zones of lighting It is part of a Digital Lighting Management DLM system and sends light level signals to control loads connected to DLM switching or dimming room controllers The LMLS 500 has a...

Страница 2: ...luorescent lamps as well as plasma screens Be sure to point the remote at a DLM IR enabled device that is within range To test see if you can put the local network into PnL using the remote from your...

Страница 3: ...has an adjustable head to accommodate multiple mounting methods and building materials or fixture walls up to 1 25 thickness NOTE For ceiling thickness lower than 5 8 the LMLS 500 must be used Fig 3 M...

Страница 4: ...r Switched Loads SENSOR PUSHBUTTONS USER Button Quick press cycle through load binding verification test Press and hold for two seconds activiate deactivate test mode Test mode automatically times out...

Страница 5: ...evel to the maximum allowed by daylighting at that time and cancel the level restriction cap set by the earlier user adjustment Increasing the light level above that set by daylighting is possible onl...

Страница 6: ...serve battery power the LMCT 100 automatically shuts OFF 10 minutes after the last key press Navigation You navigate from one field to another using up or down arrow keys The active field is indicated...

Страница 7: ...int to the desired Photosensor and press Select Point and Press Select Serial number will be different for each LMLS 500 LMLS 500 0293724909 Zon e Setup Cal i bration Zon e Settings Advanced Settings...

Страница 8: ...00 Bi Level If a Zone is selected ON When appears after scrolling down Zone Setup LMLS 500 Tri Level NEXT PRIOR DONE Load 2 Zone 2 On When Low Max Bi level and Tri Level only Press the Down arrow for...

Страница 9: ...etpoints will vary depending on light conditions 8AM 0 9AM 10AM 11AM 12AM 1PM 2PM 3PM 4PM 5PM 6PM 7PM 8PM 5 10 15 20 25 30 35 40 45 55 50 60 65 70 75 80 MAX LOW OFF HIGH MAX LOW HIGH Dead Band ON setp...

Страница 10: ...rn OFF 7 Use a light meter to measure the light level in each zone 8 Enter the measured light level at the task surface per zone in the LMCT 100 9 Select the Send button to establish communication wit...

Страница 11: ...alibration Zone Settings Advanced Settings Test Mode Choose Zone Settings Press Select Dayl ighting LMLS 500 Zone 1 Bi Level ON Setpoint OFF Setpoint ON Time Delay OFF Time Delay 35fc 53fc 20 sec 10 m...

Страница 12: ...e automatic control resumes Range Infinity or 1 to 24 hours Hold OFF The Hold Off setting selects the behavior of daylighting loads when they are turned ON by a switch or occupancy sensor If Hold Off...

Страница 13: ...CANCEL Point and Press Select LMLS 500 0293724909 Zon e Setup Cal i bration Zon e Settings Advanced Settings Con t rol Mode Press Left Right arrow to choose SEND or CANCEL Control Mode has been saved...

Страница 14: ...ack on and is not flashing the sensor is defective and must be replaced Red LED is flashing ON for three seconds OFF for one second repeating The LMLS sensor is in Control Mode Disable Use the LMCT 10...

Страница 15: ...15...

Страница 16: ...s de d fauts de mat riaux et de fabrication pour une p riode de cinq 5 ans Wattstopper ne peut tre tenu responsable de tout dommage cons cutif caus par ou li l utilisation ou la performance de ce prod...

Отзывы: