2

CONNECT THE LMRJ CABLE

The LMLS-500 receives power, and communicates 

with other DLM devices through a LMRJ cable that 

plugs into the RJ45 socket on the end of the unit. 

The LMLS-500 switches or dims electric light in response to daylight. It is important to select a location where the photosensor 

measures daylight contribution only. For proper operation the photosensor should not see any electric light contribution.
When the primary source of daylight is a window (sidelighting), the LMLS-500 is typically ceiling mounted between one to three feet 

away from the window. Figure 1a  shows a typical placement location for a sidelit application. Figure 1b  shows when the primary source 

of daylight is a skylight, mount the photosensor on the south of the light well with the lens facing north.

IR COMMUNICATION

If the photosensor is mounted at ceiling heights greater than 20’, communication with the photosensor must be through another IR-

enabled DLM device such as an occupancy sensor or a wallswitch.
Infrared signalling can be affected by high ambient light such as direct sunlight, floodlights, and some halogen or fluorescent lamps, as 

well as plasma screens. 
Be sure to point the remote at a DLM IR enabled device that is within range. To test, see if you can put the local network into PnL using 

the remote from your current position.  

•  If not successful, move closer to the IR enabled local network device and more directly in front of it, or try pointing toward a different 

IR enabled device.

•  If still not successful, the IR lenses on the DLM devices may be dirty. Clean the lenses with a soft material such as an eyeglass lens 

cleaning cloth.

Fig. 2: Attaching the LMRJ Cable

WARNING: DO NOT USE THE DLM LOCAL NETWORK TO CONTROL LOADS OTHER THAN LIGHTING IF THE 

LOAD IS NOT IN VIEW OF A PERSON AT ALL CONTROL LOCATIONS. DO NOT USE DLM TO CONTROL ANY 

LOAD THAT MIGHT BE DANGEROUS OR CAUSE A HAZARDOUS SITUATION IF ACCIDENTALLY ACTIVATED.

PLACEMENT GUIDELINES

60°

 

Mount photosensor close to window

to see only daylight contribution.

Sensor must not view

electric light output.

LMLS-500

45°

 

Window

Light Fixture

Fig. 1a: Ceiling Location 

Light Fixture

Skylight

LMLS-500

60º

Mount photosensor

on south wall of light well

with the lens facing north

45° 

Fig. 1b:  Skylight Location 

WARNING: NEVER CONNECT THE DLM LOCAL NETWORK TO A COMPUTER’S ETHERNET PORT. NEVER 

CONNECT AN ETHERNET CABLE TO A DLM DEVICE – DLM IS NOT COMPATIBLE WITH ETHERNET.

LMRJ cable

Содержание Wattstopper LMLS-500

Страница 1: ...three zones of lighting It is part of a Digital Lighting Management DLM system and sends light level signals to control loads connected to DLM switching or dimming room controllers The LMLS 500 has a...

Страница 2: ...luorescent lamps as well as plasma screens Be sure to point the remote at a DLM IR enabled device that is within range To test see if you can put the local network into PnL using the remote from your...

Страница 3: ...has an adjustable head to accommodate multiple mounting methods and building materials or fixture walls up to 1 25 thickness NOTE For ceiling thickness lower than 5 8 the LMLS 500 must be used Fig 3 M...

Страница 4: ...r Switched Loads SENSOR PUSHBUTTONS USER Button Quick press cycle through load binding verification test Press and hold for two seconds activiate deactivate test mode Test mode automatically times out...

Страница 5: ...evel to the maximum allowed by daylighting at that time and cancel the level restriction cap set by the earlier user adjustment Increasing the light level above that set by daylighting is possible onl...

Страница 6: ...serve battery power the LMCT 100 automatically shuts OFF 10 minutes after the last key press Navigation You navigate from one field to another using up or down arrow keys The active field is indicated...

Страница 7: ...int to the desired Photosensor and press Select Point and Press Select Serial number will be different for each LMLS 500 LMLS 500 0293724909 Zon e Setup Cal i bration Zon e Settings Advanced Settings...

Страница 8: ...00 Bi Level If a Zone is selected ON When appears after scrolling down Zone Setup LMLS 500 Tri Level NEXT PRIOR DONE Load 2 Zone 2 On When Low Max Bi level and Tri Level only Press the Down arrow for...

Страница 9: ...etpoints will vary depending on light conditions 8AM 0 9AM 10AM 11AM 12AM 1PM 2PM 3PM 4PM 5PM 6PM 7PM 8PM 5 10 15 20 25 30 35 40 45 55 50 60 65 70 75 80 MAX LOW OFF HIGH MAX LOW HIGH Dead Band ON setp...

Страница 10: ...rn OFF 7 Use a light meter to measure the light level in each zone 8 Enter the measured light level at the task surface per zone in the LMCT 100 9 Select the Send button to establish communication wit...

Страница 11: ...alibration Zone Settings Advanced Settings Test Mode Choose Zone Settings Press Select Dayl ighting LMLS 500 Zone 1 Bi Level ON Setpoint OFF Setpoint ON Time Delay OFF Time Delay 35fc 53fc 20 sec 10 m...

Страница 12: ...e automatic control resumes Range Infinity or 1 to 24 hours Hold OFF The Hold Off setting selects the behavior of daylighting loads when they are turned ON by a switch or occupancy sensor If Hold Off...

Страница 13: ...CANCEL Point and Press Select LMLS 500 0293724909 Zon e Setup Cal i bration Zon e Settings Advanced Settings Con t rol Mode Press Left Right arrow to choose SEND or CANCEL Control Mode has been saved...

Страница 14: ...ack on and is not flashing the sensor is defective and must be replaced Red LED is flashing ON for three seconds OFF for one second repeating The LMLS sensor is in Control Mode Disable Use the LMCT 10...

Страница 15: ...15...

Страница 16: ...s de d fauts de mat riaux et de fabrication pour une p riode de cinq 5 ans Wattstopper ne peut tre tenu responsable de tout dommage cons cutif caus par ou li l utilisation ou la performance de ce prod...

Отзывы: