OVERLOAD PROTECTION

The occupancy sensor has a built in overload protection function that will automatically turn 

OFF

 the control output when the load 

current exceeds 200mA.  The sensor LEDs will then blink rapidly (~ 10Hz) to provide a visual indication of an overload condition.  When 

the load current is corrected or returns to normal, the control output will turn back 

ON

.

TROUBLESHOOTING

For any unexpected operation:

1.  Check DIP Switch settings.
2.  Make sure the switches are set according to the defined settings in the DIP Switch setting chart.

Lights do not turn on when entering the room.

Neither LED Flashes.

1.  Check that the circuit breaker has been turned back on.
2.  Check all sensor and power pack wire connections.
3.  Check for 24VDC input to the sensor between the red and black low voltage wires.

•  If 24VDC is present, replace the sensor.
•  If 24VDC is not present, check the high voltage connections to the power pack.
•  If high voltage connections are good and high voltage is present, replace the power pack.

Red LED does not flash.

1.  When power is initially applied to the sensor, there is a warm-up period of 30 to 60 seconds before the LED becomes active.
2.  Make sure PIR sensitivity is set to 100% (DIP switch #5 is in the “off” position).

Green LED does not flash.

Ultrasonic sensitivity setting may need to be increased. Turn adjustment trimpot clockwise  until the LED begins to flash when movement 

occurs.

Green LED is on steady.

Check ultrasonic sensitivity trimpot. Fully counterclockwise position is the override for the sensor. Turn trimpot clockwise until LED 

flashes only when movement occurs in the desired coverage area.

Red and Green LEDs flash.

1.  Check all sensor and power pack connections.
2.  Check for 24VDC at the power pack blue and black wire connections to sensor while sensor is active.

•  If there is no voltage, replace the sensor.
•  If there is voltage, check for 24VDC between the blue and black wire at the power pack.  If 24VDC is present and the relay is not 

closing, replace it.

•   If 24VDC is not present, check for a break in the low voltage wiring.

3.  If LED is flashing rapidly (~10Hz), an overload condition exists. When this is corrected, the sensor  will return to normal operation. 

Check the blue wire connection. If necessary, replace the power pack.

Lights do not turn off automatically.

Green LED flashes.

Reduce ultrasonic sensitivity by turning adjustment pot counter-clockwise until it only flashes when movement occurs.

Red LED flashes briefly and Green LED does not flash.

Check to see if you have used the Manual Switch connection. Do not connect anything to this terminal if you are not using a low voltage 

momentary switch between the sensor and power pack.

Red LED randomly flashes.

Set PIR sensitivity to minimum by turning DIP switch 5 to the “on” position.

Lights do not turn off.

1.  Check all sensor and power pack wire connections.
2.  Disconnect power pack blue wire.

•  If lights do not turn off, check power pack wiring.  Replace the power pack if necessary.
•  If lights turn off, the problem may be the sensor or wiring between the sensor and power pack.

3.  Reconnect the blue wire.

•  Turn sensitivity and time delay to minimum, and allow the sensor to time out.
•  If lights turn off, the sensor is working properly – adjust sensitivity and time delay for the sensor.
•  If lights do not turn off, check the wiring between the sensor and power pack.
•  If wiring is correct, replace the sensor.

Содержание Wattstopper DT-205

Страница 1: ...nology occupancy sensors combine advanced passive infrared PIR and ultrasonic technologies into one unit The combination of these technologies helps to eliminate false triggering problems even in diff...

Страница 2: ...required Refer to the wiring diagram on the next page for the following procedures Connect the LOW VOLTAGE RED wire 24VDC from power pack to the red wire on the sensor BLACK wire Return from power pa...

Страница 3: ...e ultrasonic sensor have a person walk back and forth at the far end of the space Increase or decrease mounting angle as needed until the desired coverage is achieved Tighten the Tightening Screw to h...

Страница 4: ...gger After the time delay elapses and the lights turn OFF detection by the selected technology within the number of seconds indicated turns the lights back ON MANUAL ON FUNCTION The Manual ON function...

Страница 5: ...occurs in the desired coverage area Red and Green LEDs flash 1 Check all sensor and power pack connections 2 Check for 24VDC at the power pack blue and black wire connections to sensor while sensor is...

Страница 6: ...ast or incandescent BZ 150 Power Pack 120 277VAC 50 60Hz 20A ballast or incandescent with Hold On and Hold Off capability BZ 200 Power Pack 120 277VAC 50 60 Hz 20A Ballast ELV MLV Incandescent LED 16A...

Страница 7: ...40 kHz PORT E Le DT 205 a une port e elliptique La port e indiqu e dans le sch ma repr sente un mouvement de marche une hauteur de 3 m tres 10 pieds Pour les b timents avec une activit plus faible ou...

Страница 8: ...250 doivent tre mis la terre pour garantir l int grit du signal et non pour une mise la terre de s curit Bloc d alimentation Contr le Bleu Commun Noir 24VDC Rouge VersAutre D tecteur s Gris DT 205 d...

Страница 9: ...le passe tout d abord par une p riode de r chauffement de 30 secondes Avant d effectuer des r glages assurez vous que les meubles de la zone de travail sont install s que les circuits d clairage sont...

Страница 10: ...re pour activer la charge Le d tecteur maintient la charge activ e en fonction de l activit des occupants Une fois la temporisation coul e si aucun mouvement n est d tect pendant la p riode de re d cl...

Страница 11: ...on sur le d tecteur pendant que le d tecteur est activ En l absence de tension remplacez le d tecteur S il y a de la tension contr lez la pr sence de 24 VCC entre les fils bleu et noir au niveau du bl...

Страница 12: ...A avec une capacit de Maintien de l tat marche Maintien de l arr t BZ 200 Bloc d alimentation 120 277VCA 50 60 Hz Ballast ELV MLV Incandescent DEL 20A E Ballast CFL Prise de courant 16A BZ 250 Bloc d...

Страница 13: ...de cobertura el ptico La cobertura que se muestra representa el movimiento para caminar a una altura de montaje de 10 pies 3 04 metros En las reas de edificios con menos nivel de actividad o con obst...

Страница 14: ...es adicionales Gris DT 205 Sensor de ocupaci n de bajo voltaje MONTAJE DEL SENSOR Los sensores DT 205 pueden montarse a la pared o al cielo raso con el soporte giratorio suministrado y con la placa de...

Страница 15: ...stalados de que los circuitos de iluminaci n est n encendidos y de que los sistemas de HVAC est n en la posici n de anulaci n encendido Los sistemas VAV deben configurarse con su m ximo caudal de aire...

Страница 16: ...ue se presiona el interruptor la carga cambia el estado El funcionamiento del sensor en relaci n con el interruptor accionado manualmente se determina seg n la configuraci n del interruptor DIP para l...

Страница 17: ...amente contraria a las manecillas del reloj es la anulaci n del sensor Gire el potenci metro en el sentido de las manecillas del reloj hasta que la luz LED destelle solamente cuando se produce el movi...

Страница 18: ...n respecto a la p rdida de propiedad renta o ganancias o al costo de extracci n instalaci n o reinstalaci n WARRANTY INFORMATION INFORMATIONS RELATIVES LA GARANTIE INFORMACI N DE LA GARANT A 3 Vuelva...

Отзывы: