background image

3

MOUNTING

 (continued)

Physical Mounting

The following information applies to physically mounting the unit.

•  You can mount the LMJA-8125/8300 in any orientation. Horizontal mounting (as shown) is strongly recommended to achieve 

maximum heat dissipation and meet the operating temperature upper limit. Any other mounting orientation reduces this upper limit.

•  Mounting on a 35mm wide DIN rail is recommended. The LMJA-8125/8300 unit base has a molded DIN rail slot and locking clip. 

DIN rail mounting ensure alignment of the connectors between all devices.

•  If DIN rail mounting is impractical, you can use screws in mounting tabs on the controller (see next page)
•  The LMNC-ENC1 is an optional DIN rail equipped enclosure. The LMNC-ENC1 provides an integral 120VAC receptacle, conduit 

connection points and protection for the LMJA-8xxx. It is designed for applications where code or the local AHJ requires that low 

voltage wiring such as control and communication wiring be run inside conduit, or where needed for customer specifications. See 

the instructions provided with the LMNC-ENC1 for more information.

•  The LMJA-8125/8300 controller can also be mounted in an LMNC enclosure, where multiple NB-Routers and an NB-Switch are 

used

To mount on third-party DIN rail

The following procedure provides step-by-step DIN rail mounting instructions for the LMJA-8125/8300. It is recommended to leave 2 

inches of clearance above and below the unit.

1.  Pull the controller’s locking clip down.
2.  Tilt the controller to hook over the DIN rail.
3.  Push down and in on the unit, fastening to the rail.
4.  Push the locking clip up to secure.
5.  Mount any option module (RS-485 Module) onto the DIN rail in the same way.
6.  Carefully secure both ends of the final assembly with DIN rail end-clips provided by the DIN rail vendor.

NOTE: 

To remove a unit from the DIN rail, pull 

down its locking clip, then swing the bottom 

out and lift the unity away from the DIN rail.

Содержание Wattstopper DLM LMJA-8 Series

Страница 1: ...and return any damaged components for immediate repair or replacement Included in this Package Included in this package you should find the following items 1 DLM LMJA 8125 8300 controller unit with m...

Страница 2: ...ocation that allows clearance for wiring servicing and module removal Environmental Requirements Note the following requirements for the LMJA 8125 8300 controller mounting location This product is int...

Страница 3: ...de or the local AHJ requires that low voltage wiring such as control and communication wiring be run inside conduit or where needed for customer specifications See the instructions provided with the L...

Страница 4: ...cale Verify all measurements before drilling Tab Mounting Dimensions Measurements shown below are in inches and mm NOTE DIN rail mounting is recommended over tab mounting 1 The LMJA 8125 8300 controll...

Страница 5: ...ord w ttstopper Note that both the user name and password are case sensitive Click the Login button Logins with individual permissions can be customized for different users Refer to the Operation Manu...

Страница 6: ...for direct connection to the Segment Manager proceed as follows 1 Click on the Start menu and type network sharing center Then Click on Network and Sharing Center in results 2 Click Local Area Connect...

Страница 7: ...er the IP address and Subnet mask Set the PC to 192 168 1 xxx where xxx is any number between 001 and 255 and is not the same as the Segment Manager Set the subnet mask to 255 255 255 0 7 Click OK the...

Страница 8: ...tom board visible only with cover removed From left to right these LEDs include Status STATUS Heartbeat BEAT Serial Ports see USB Ports section on page 10 for explanation Ethernet Ports SEC PRI Ethern...

Страница 9: ...s Off repeating Some scenarios where the BACKUP LED is used include USB Drive Inserted A USB flash drive is inserted in the USB 2 0 port to either backup a commissioned unit to the USB drive or to res...

Страница 10: ...iates a controlled shutdown of the controller ensuring that all station data is preserved This provides an alternative to the platform stop station command while connected online with controller WIRIN...

Страница 11: ...shown on controller 1 RS485 ports and bias switches 2 Ethernet ports 10 100 Mbit RJ 45 3 Earth ground and 24V power input 4 WLAN is NOT enabled 2 4 1 3 SEC RS485 A COM 1 RS485 B COM 2 END BIA MID ACC...

Страница 12: ...150 Ohm termination resistor MID RS485 biasing or termination 47 5K bias resistors with no termination resistor Often adding RS 485 biasing can improve communications by eliminating indeterminate idle...

Страница 13: ...ions Wiring Before connecting cables provide strain relief for them to prevent damage to the LMJA 8xxx Connect communications wiring to the LMJA 8xxx see page 11 which include RJ 45 Ethernet for PC or...

Страница 14: ...168 1 140 This address can be changed See the Segment Manager 2 4 Operation Manual for details The subnet mask is 255 255 255 0 The factory default IP address for LAN2 on a LMJA 8xxx is 192 168 5 140...

Страница 15: ...ATUS LED is located to the right of the heartbeat BEAT LED and is green This LED provides a CPU machine status check and should be lit when the LMJA 8xxx is powered If the STATUS LED is not lit while...

Страница 16: ...0 rooms common spaces WIRING EXAMPLES continued EXAMPLE Three story building with no more than 40 rooms common spaces per floor Ethernet cable to LAN PC or BAS Segment Networks 1 2 and 3 LMJA 8xxx LMJ...

Страница 17: ...NB Switch NB Routers Power Supply 1st Floor Rooms 141 180 2nd Floor Rooms 201 240 2nd Floor Rooms 241 280 3rd Floor Rooms 301 340 4th Floor Rooms 401 440 LMJA 8xxx 5th Floor Rooms 501 540 Ethernet Dai...

Страница 18: ...ith the ability to physically connect a computer to the lighting control network when needed for service or to purchase our Remote Access cellular based service RACCESS OPTION 2 Virtual network isolat...

Страница 19: ...ivalency Device equivalency Connected devices With 0 LMFC 011s or LMRCs used for scheduling functions 1 10 Count connected devices With 1 24 LMFC 011s or LMRCs connected 3 20 Count connected devices W...

Страница 20: ...ings and Certifications The LMJA 8125 8300 controller has the following agency listings compliances and certifications UL 916 Energy Management Equipment Edition 4 FCC Part 15 Class B Federal Communic...

Страница 21: ...ipment for measurement control and laboratory use PASS INITIATING A CONTROLLER SHUTDOWN When locally servicing an installed and configured commissioned unit use this feature before removing power NOTE...

Страница 22: ...rofits ou aux co ts d enl vement d installation ou de r installation Wattstopper garantiza que sus productos est n libres de defectos en materiales y mano de obra por un per odo de un 3 a o No existen...

Отзывы: