2

PREPARATION 

(continued) 

Inserting or Removing the Micro SD Card Installation

Before mounting a new controller, you must insert the included microSD flash memory card. Note the card has the unique Niagara 

identity (host ID) for the unit, set at the factory. ALL power to the controller must be removed. If the unit is currently running, initiate a 

controller shutdown.

1.  Carefully slide the plastic microSD card shutter open. The shutter should remain captive in the base, revealing the microSD card 

socket.

2.  To insert the microSD card, slide it into the card carrier, label side up, until the spring catch engages. If properly inserted, the card is 

behind the shutter track.

3.  To remove the microSD card, push it in, until the spring release pushes it partially out of the card carrier. Grasp the card, pull it 

completely out of the unit and store it in a static-free protective case.

4.  Carefully slide the card shutter back over the card carrier opening, until it clicks into place. When properly closed, the shutter should 

not protrude behind the mounting base.

NOTE: 

Data on the microSD card is encrypted. If you swap in a card from a previously configured unit, you must change the LMJA-

8125/8300 system passphrase on the platform to match the passphrase on the new microSD card. Typically, the microSD card never 

needs removal. However, in the case where a controller has been electrically damaged or found faulty, you can remove the card and 

install it in another like unit, so it can become a functional replacement.

1.  Access shutter for microSD card (slide down/up to 

open/close)

2.  Card carrier inside controller
3.  MicroSD card to insert or remove from card carrier

MOUNTING

Mount the LMJA-8125/8300 controller in a location that allows clearance for wiring, servicing, and module removal. 

Environmental Requirements

Note the following requirements for the LMJA-8125/8300 controller mounting location:

•  This product is intended for indoor use only. Altitude to 6,562 ft (2,000m).
•  Ambient conditions must be within the range of: Operating Temperature: -4°F to 140°F (-20°C to 60°C), Storage Temperature: -40°F 

to 185°F (-40°C to 85°C)

•  Relative Humidity: 5% to 95% non-condensing, Pollution Degree 3
•  Supply (mains) voltage requirements: Allowable voltage fluct/- 10%
•  Do not expose the unit to ambient conditions outside of the range of 0ºC (32º F) to 50ºC (122º F) and relative humidity outside the 

range 5% to 95% non-condensing.

•  If mounting inside an enclosure, that enclosure should be designed to keep the unit within its required operating range considering 

a 24-watt dissipation by the controller, plus dissipation from any other devices installed in the same enclosure. This is especially 

important if the controller is mounted inside an enclosure with other heat producing equipment.

•  Do not mount the unit:

 

In an area where excessive moisture, corrosive fumes, or explosive vapors are present

 

Where vibration or shock is likely to occur

 

In a location subject to electrical noise, including the proximity of large electrical conductors, electrical machinery, welding 

equipment, spark igniters, and variable frequency drives, etc.

MATERIAL AND TOOLS REQUIRED

• 

One of the following:

 

UL Listed, Class 2, 24VAC transformer, rated at minimum of 24VA. A dedicated transformer is required (cannot power additional 

equipment), -OR-

 

24VDC power supply, capable of supplying at least 1A (24W), -OR-

 

NB-PS1 wall-mount AC power adapter with barrel connector plug

• 

DIN rail, type NS35/7.5 (35mm x 7.5mm_ and DIN rail end-clips (stop clips), recommended for any installation with option modules. 

Controller is also panel mountable.

• 

Suitable tools, fasteners, and accessories for mounting

Содержание Wattstopper DLM LMJA-8 Series

Страница 1: ...and return any damaged components for immediate repair or replacement Included in this Package Included in this package you should find the following items 1 DLM LMJA 8125 8300 controller unit with m...

Страница 2: ...ocation that allows clearance for wiring servicing and module removal Environmental Requirements Note the following requirements for the LMJA 8125 8300 controller mounting location This product is int...

Страница 3: ...de or the local AHJ requires that low voltage wiring such as control and communication wiring be run inside conduit or where needed for customer specifications See the instructions provided with the L...

Страница 4: ...cale Verify all measurements before drilling Tab Mounting Dimensions Measurements shown below are in inches and mm NOTE DIN rail mounting is recommended over tab mounting 1 The LMJA 8125 8300 controll...

Страница 5: ...ord w ttstopper Note that both the user name and password are case sensitive Click the Login button Logins with individual permissions can be customized for different users Refer to the Operation Manu...

Страница 6: ...for direct connection to the Segment Manager proceed as follows 1 Click on the Start menu and type network sharing center Then Click on Network and Sharing Center in results 2 Click Local Area Connect...

Страница 7: ...er the IP address and Subnet mask Set the PC to 192 168 1 xxx where xxx is any number between 001 and 255 and is not the same as the Segment Manager Set the subnet mask to 255 255 255 0 7 Click OK the...

Страница 8: ...tom board visible only with cover removed From left to right these LEDs include Status STATUS Heartbeat BEAT Serial Ports see USB Ports section on page 10 for explanation Ethernet Ports SEC PRI Ethern...

Страница 9: ...s Off repeating Some scenarios where the BACKUP LED is used include USB Drive Inserted A USB flash drive is inserted in the USB 2 0 port to either backup a commissioned unit to the USB drive or to res...

Страница 10: ...iates a controlled shutdown of the controller ensuring that all station data is preserved This provides an alternative to the platform stop station command while connected online with controller WIRIN...

Страница 11: ...shown on controller 1 RS485 ports and bias switches 2 Ethernet ports 10 100 Mbit RJ 45 3 Earth ground and 24V power input 4 WLAN is NOT enabled 2 4 1 3 SEC RS485 A COM 1 RS485 B COM 2 END BIA MID ACC...

Страница 12: ...150 Ohm termination resistor MID RS485 biasing or termination 47 5K bias resistors with no termination resistor Often adding RS 485 biasing can improve communications by eliminating indeterminate idle...

Страница 13: ...ions Wiring Before connecting cables provide strain relief for them to prevent damage to the LMJA 8xxx Connect communications wiring to the LMJA 8xxx see page 11 which include RJ 45 Ethernet for PC or...

Страница 14: ...168 1 140 This address can be changed See the Segment Manager 2 4 Operation Manual for details The subnet mask is 255 255 255 0 The factory default IP address for LAN2 on a LMJA 8xxx is 192 168 5 140...

Страница 15: ...ATUS LED is located to the right of the heartbeat BEAT LED and is green This LED provides a CPU machine status check and should be lit when the LMJA 8xxx is powered If the STATUS LED is not lit while...

Страница 16: ...0 rooms common spaces WIRING EXAMPLES continued EXAMPLE Three story building with no more than 40 rooms common spaces per floor Ethernet cable to LAN PC or BAS Segment Networks 1 2 and 3 LMJA 8xxx LMJ...

Страница 17: ...NB Switch NB Routers Power Supply 1st Floor Rooms 141 180 2nd Floor Rooms 201 240 2nd Floor Rooms 241 280 3rd Floor Rooms 301 340 4th Floor Rooms 401 440 LMJA 8xxx 5th Floor Rooms 501 540 Ethernet Dai...

Страница 18: ...ith the ability to physically connect a computer to the lighting control network when needed for service or to purchase our Remote Access cellular based service RACCESS OPTION 2 Virtual network isolat...

Страница 19: ...ivalency Device equivalency Connected devices With 0 LMFC 011s or LMRCs used for scheduling functions 1 10 Count connected devices With 1 24 LMFC 011s or LMRCs connected 3 20 Count connected devices W...

Страница 20: ...ings and Certifications The LMJA 8125 8300 controller has the following agency listings compliances and certifications UL 916 Energy Management Equipment Edition 4 FCC Part 15 Class B Federal Communic...

Страница 21: ...ipment for measurement control and laboratory use PASS INITIATING A CONTROLLER SHUTDOWN When locally servicing an installed and configured commissioned unit use this feature before removing power NOTE...

Страница 22: ...rofits ou aux co ts d enl vement d installation ou de r installation Wattstopper garantiza que sus productos est n libres de defectos en materiales y mano de obra por un per odo de un 3 a o No existen...

Отзывы: