16
The LMJA-8125/8300 can be used in conjunction with multiple NB-Routers and an NB-Switch. These components are usually housed
inside an LMNC DLM Network Component Enclosure. Each router communicates with one segment. There is a maximum of 300 rooms
or common spaces controlled by a single LMJA-8xxx, and the maximum of 40 per segment still applies. Therefore a typical application
with close to 300 rooms/spaces (and up to 2000 DLM devices) might use between seven and nine routers, depending on how many
devices are connected in each segment. (As mentioned previously, Wattstopper recommends not fully loading a controller to maximum
capacity, to allow for future changes or additions to the segment.)
EXAMPLE: Four story building with some floors having more than 40 rooms/common spaces
WIRING EXAMPLES
(continued)
EXAMPLE: Three story building with no more than 40 rooms/common spaces per floor
Ethernet cable to
LAN, PC or BAS
Segment Networks
1, 2, and 3
LMJA-8xxx
LMJA-NPB-2X-485
1st Floor
2nd Floor
3rd Floor
LMBC-300
LMBC-300
LMBC-300
LMBC-300
LMBC-300
LMBC-300
LMBC-300
Daisy-chain to LMBC/LMCP/LMZCs
NO MORE THAN 40 TOTAL
Daisy-chain to LMBC/LMCP/LMZCs
NO MORE THAN 40 TOTAL
Daisy-chain to LMBC/LMCP/LMZCs
NO MORE THAN 40 TOTAL
LMBC-300
LMBC-300
LMJA-8xxx
1st Floor – Rooms 101-140
Ethernet
LMBC-300, LMCP, or LMZC-301
Daisy Chain
NO MORE THAN 40 TOTAL
Daisy Chain
NO MORE THAN 40 TOTAL
Daisy Chain
NO MORE THAN 40 TOTAL
Daisy Chain
NO MORE THAN 40 TOTAL
Daisy Chain
NO MORE THAN 40 TOTAL
Daisy Chain
NO MORE THAN 40 TOTAL
Wattstopper recommends a maximum of
32
NB-Switch
NB-Routers
Power Supply
LMNC
1st Floor – Rooms 141-180
2nd Floor – Rooms 201-240
2nd Floor – Rooms 241-280
3rd Floor – Rooms 301-340
4th Floor – Rooms 401-440