3
DCLV2
+24VDC
Common
Relais externe 1
Ground
Ground
0-10V
0-10V
Violet
Gray
Control
Control
Common
+24VDC
Neutral
Red
Black
Blue
Black
Red
Red
Line
White
Switch
(optional)
Gray
Brown
Orange
Violet
Gray
0-10VDC Dimming
Ballast Required
Push
to Test
Cut jumper loop to use with Normally Closed
test switch, fire alarm panel, security panel, other
ELCU-200
Remote
Activation
Normal Power
Emergency
Power
(Black18AWG)
Normal Neutral
(White 18AWG)
Normal Switched Sense
(Red 18AWG)
Emergency Power In
(Black12AWG)
Emergency Neutral
(White 18AWG)
Emergency Power Out
(Red 12AWG)
Emergency Line
Emergency Neutral
Emergency
Lighting
LOAD 1
L
o
a
d
Typical
3 Wire
Occupancy
Sensor
BZ-XXX
POWER PACK
Normal Power Sense
DCLV2 with ELCU-200
The DCLV2 can be used with the ELCU-200 to turn the lights to full ON upon an emergency. The DCLV2 opens the 0-10V circuit at time
of power loss. If the Emergency lighting was in a dimmed state when the normal power was lost, the emergency lighting will be at 100%
versus last dimmed level. The ELCU-200 or some like device needs to be involved in the overall emergency management system to
monitor the loss of normal power so that the 0-10 volt emergency lighting will not only be ON but ON at 100%.