LEGRAND Wattstopper DCLV2 Скачать руководство пользователя страница 1

Wattstopper

 

®

Decorator Style 0-10V Controller
Gradatateur 0-10 V style Decorateur
Controlador de 0 a 10 V Decorator Style

Installation Instructions • Instructions d’Installation • Instrucciones de Instalación

No: 27465 – 08/19  rev. 4

Catalog Number • Numéro de Catalogue • Número de Catálogo: DCLV2 

Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China

SPECIFICATIONS

Power Supply .......................................Wattstopper Power Pack

Rating .............................................................. 24VDC, 16mA

Control outputs

For 0–10V Dimming Ballasts:

Sink ................................................................up to 50mA
Maximum voltage .................................................9.5VDC
Minimum voltage ................................................0.75VDC

Operating Temperature ....................... 32° to 104°F (0° to 40°C)

DESCRIPTION

The DCLV2 0–10V dimming wallbox controller includes a Manual On feature or partial Auto On.
The DCLV2 must be used with BZ Series power packs and can be combined with occupancy sensors.

Features

•  Control electronic ballasts and drivers for LED systems.
•  Sink up to 50mA, allowing the product to control up to 100 ballasts wired in parallel (each ballast sourcing 0.5mA).
•  0–10V output ranges at a minimum between 0.75VDC and 9.5VDC.
•  Able to receive a sensor input.
•  Operating supply voltage 24VDC: Class-2 device powered directly from an external source.
•  Wattstopper BZ series for 0-10V ballast control.

INSTALLATION

NOTE: INSTALL IN COMPLIANCE WITH ALL APPLICABLE CODES & STANDARDS.

Failure to follow these instructions may cause personal injury or equipment damage.
The DCLV2 is a Class 2 product. A low voltage cable with the appropriate number of conductors must be installed. For ease of 

installation, manufacturer recommends use of a deep wall box.

1.  Disconnect power to circuit by turning circuit breaker OFF before installation.
2.  Remove the existing wall plate and switch, if one is present. If there is an existing line voltage switch the wiring must be converted 

to low voltage in order to use the original wall box location for the DCLV2. Alternatively, the existing line voltage switch may 

remain, however a new wall box must be installed for the DCLV2 according to NEC requirements.

3.  Install power pack to control the desired lighting circuit.
4.  Strip existing wires 1/4”. If two wires will be connected to the same terminal, both wires must be the same gauge. Connect wires 

as appropriate for your application. See the wiring diagrams on the following page.

5.  Attach the wall plate.
6.  Switch the circuit breaker back ON.

Содержание Wattstopper DCLV2

Страница 1: ...sor input Operating supply voltage 24VDC Class 2 device powered directly from an external source Wattstopper BZ series for 0 10V ballast control INSTALLATION NOTE INSTALL IN COMPLIANCE WITH ALL APPLIC...

Страница 2: ...e DCLV2 is dimming down The OFF to ON transition is immediate WIRING EXAMPLES LIGHTING CONTROL Neutral Hot White Black Red Red Fixture Ground Red Black Blue Orange Brown Gray Low Voltage Wires 24VDC 0...

Страница 3: ...cy Neutral White 18AWG Emergency Power Out Red 12AWG Emergency Line Emergency Neutral Emergency Lighting LOAD 1 L o a d Typical 3 Wire Occupancy Sensor BZ XXX POWER PACK Normal Power Sense DCLV2 with...

Страница 4: ...ress and hold LEARN again for four seconds to exit the setup binding mode and return to normal operation NOTE By default or after a reset Partial On is enabled with a fixed value of 50 To disable the...

Страница 5: ...1 4 de pouce Si deux c bles sont branch s sur la m me borne les deux c bles doivent tre du m me calibre Branchez les c bles en fonction des besoins de votre application Consultez les sch mas de c blag...

Страница 6: ...il convient de tenir compte des l ments suivants Les c bles orange marron et gris ne sont pas utilis s sur le BZ 150 et le BZ 250 et une protection doit donc tre plac e leur extr mit L interrupteur Ma...

Страница 7: ...0 10V Violet Gris Commande Commande Commun 24VCC Neutre Rouge Noir Bleu Noir Rouge Rouge Sous Tension Blanc Interrupteur optionnel Gris Marron Orange Violet Gris Ballast e ballast driver de gradation...

Страница 8: ...ENTISSAGE pendant quatre secondes pour quitter le mode configuration liaison et revenir au fonctionnement normal NOTE Par d faut ou apr s une r initialisation le mode Marche partielle est activ avec u...

Страница 9: ...istentes Si se conectan dos cables en el mismo terminal ambos cables deben ser del mismo calibre Conecte los cables seg n corresponda para su aplicaci n Consulte los diagramas de cableado en la p gina...

Страница 10: ...nterruptor de Encendido manual autom tico de las unidades BZ 150 y BZ 250 debe dejarse en la posici n de Encendido autom tico El DCLV2 cordina la funci n manual Las unidades BZ 200 y BZ 250 deben cone...

Страница 11: ...e cuatro segundos para salir del modo de configuraci n enlace y volver al funcionamiento normal NOTE De manera predeterminada o tras realizar un restablecimiento el modo de Encendido parcial se activa...

Страница 12: ...acci n instalaci n o reinstalaci n WARRANTY INFORMATION INFORMATIONS RELATIVES LA GARANTIE INFORMACI N DE LA GARANT A DCLV2 con ELCU 200 El DCLV2 se puede utilizar con el ELCU 200 para encender las lu...

Отзывы: