40
6.5
POWER ON/OFF menu
When the EPS is on, it is possible to access a menu called POWER ON/OFF by pressing the ON/OFF pushbutton for less
than 0,5 seconds.
The choices that can be made in this menu are the following:
L1 phase (**)
Press the ENTER key to access the submenu in which it is possible to choose whether to
turn phase L1 on or off independently of the others.
Press the ARROW UP/DOWN keys to choose the ON or the OFF value. Press the ENTER key
to confirm the value. Press the ESC key to leave the submenu.
L2 phase (**)
Press the ENTER key to access the submenu in which it is possible to choose whether to
turn phase L2 on or off independently of the others.
Press the ARROW UP/DOWN keys to choose the ON or the OFF value. Press the ENTER key
to confirm the value. Press the ESC key to leave the submenu.
L3 phase (**)
Press the ENTER key to access the submenu in which it is possible to choose whether to
turn phase L3 on or off independently of the others.
Press the ARROW UP/DOWN keys to choose the ON or the OFF value. Press the ENTER key
to confirm the value. Press the ESC key to leave the submenu.
UPS
Press the ENTER key to access the submenu to switch the EPS off.
Press the ENTER key again to switch the equipment off. Press the ESC key to leave the
submenu.
Hot swap
Press the ENTER key to access a submenu to make the hot-swap substitution of the power
modules.
CAUTION
This operation CANNOT BE PERFORMED
(**) Available with the inverter set up as three independent phases only
6.6
Switching off the EPS
CAUTION
The shutdown procedure must be applied exclusively if the load is off or does not need to be supplied by the EPS.
There are two possible ways to shut down the UPS.
It is possible to shut down the UPS from the POWER ON/OFF menu or it is possible to perform the following procedure:
1. Keep the ON/OFF key pressed for at least two seconds.
2. The display shows the text "Turn off the UPS?". Press the ENTER key.
3. Wait for the shutdown operations to complete.
If a prolonged shutdown is planned, apply what is prescribed in chapter 9.
6.7
Switching on the EPS
The operator can turn the equipment on with the following procedure:
1. Press the ON/OFF key.
2. When the display shows the text “<ENTER> to confirm UPS turn ON”, press the ENTER key. If no operation is carried out
within 30 seconds, the EPS turns off.
If the display shows the message "WARNING: different UPS setup! <ENTER> to confirm UPS turn on”, the EPS setup is
different from the last power up. A skilled technican must check the setup before confirming the power up.
3. Wait for the power up operations to complete. The load is only supplied when the bar with the text “UPS initialize...”
displayed reaches the end and the main screen appears.
6. Control panel
Содержание Trimod MCS 10
Страница 1: ...Item LE10960AA 01 19 01 CT Trimod MCS User manual ...
Страница 2: ...2 UK ENGLISH 3 Trimod MCS ...
Страница 16: ...16 3 3 Models Trimod MCS 3 5 10 Trimod MCS 7 15 3 Technological description ...
Страница 17: ...Trimod MCS User manual 17 Trimod MCS 30 Trimod MCS 20 ...
Страница 18: ...18 Trimod MCS 40 Trimod MCS 60 Trimod MCS 80 3 Technological description ...
Страница 58: ...58 ...
Страница 59: ...Trimod MCS User manual 59 ...