Trimod HE
U
ser manual
35
STATUS
INDICATOR
POWER MODULE
LED
AUDIBLE
NOTIFICATION
STATUS
MESSAGE
UPS STATUS DESCRIPTION AND
OPERATING ADVICE
ORANGE
Long intermittent
GREEN
Steady
-
Make
Maintenance
Contact the LEGRAND Technical
Support Service
ORANGE
Long intermittent
GREEN
Steady
-
Check
Batteries
A skilled technician must
check the batteries status
ORANGE
Quick flashing
ORANGE
Flashing
-
Maintenance
Bypass
Manual bypass mode
ORANGE
Short and double
intermittent with pause
ORANGE
Steady
Short and double
intermittent
with pause
RUNTIME
RESERVE!
Autonomy reserve during battery
mode. Short time left before the
load is powered by the bypass line.
RED
Steady
RED
Steady only on the
module with the
fault
Quick
intermittent
FAULT
CHARGER
Battery charger faulty on
at least one power module.
A skilled technician must replace
the faulty module.
RED
Steady
RED
Steady only on the
module with the fault
Quick
intermittent
FAULT
MODULE
A skilled technician must replace
the faulty power module
RED
Quick flashing
ORANGE
Flashing
Quick
intermittent
BATTERIES KO
Batteries faulty or not connected.
A skilled technician must check the
batteries.
RED
Quick flashing
RED
Quick flashing
Quick
intermittent
BATTERY
DISCONNECTED
Batteries faulty or not connected.
A skilled technician must check
the batteries.
RED
Quick flashing
RED
Short and double
intermittent with
pause
Quick
intermittent
BATTERY
RUNAWAY
Excessive battery voltage.
If the alarm persists over time
a skilled technician must check the
batteries.
RED
Quick flashing
RED
Short and double
intermittent with
pause
Quick
intermittent
HVBUS
RUNAWAY FAIL
Contact the LEGRAND Technical
Support Service
RED
Quick flashing
RED
Steady
Quick
intermittent
OUT DC
LEVEL FAIL
Reset the power module error from
the control panel in Service Mode
(paragraph 5.4.3) and turn on the
UPS. If the error persists, one or
more power modules are faulty and
a skilled technician must replace
them.
RED
Quick flashing
RED
Short and double
intermittent
with pause only on the
module in alarm mode
Quick
intermittent
OVERHEAT
Overheating of one
or more power modules.
Check the functioning of the
module fans and clean the air
intake grilles.
RED
Quick flashing
RED
Short and double
intermittent with
pause only on the
overloaded module
Quick
intermittent
OVERLOAD
Overload on one or
more power modules.
Check the applied load.
RED
Quick flashing
-
Quick
intermittent
CM FAILURE
Contact the LEGRAND Technical
Support Service
RED
Quick flashing
-
Quick
intermittent
Reference
Error!
or
Reference
Warning
Contact the LEGRAND Technical
Support Service
RED
Quick flashing
-
Quick
intermittent
BACKFEED
Contact the LEGRAND Technical
Support Service