Bypass
Bypass Enable
If enabled, the UPS manages the bypass intervention automatically.
If disabled, the UPS never switches to bypass mode so in the case of an
extended overload or in the case of failure and absence of redundancy,
the UPS turns off.
Forced Mode
If enabled, the UPS activates the bypass permanently
DIP Speed
This makes it possible to vary the sensibility of the switching circuit:
- SLOW: indicated for loads not sensitive to voltage variations and that
cause peaks of current
- STANDARD: normal mode
- FAST: for all loads that are extremely sensible to voltage variations
Off-line Mode
If enabled, the UPS functions in eco mode.
During the functioning, the load is powered directly by the automatic
bypass circuit. If there is a power failure or the voltage input tolerance
is exceeded, the UPS activates the inverter thereby powering the load
through the batteries.
Start-up on Bypass
If enabled, on mains start-up the initial powering of the load occurs via
bypass.
If disabled, the inrush current is managed by the inverter as in a battery
start-up.
CAUTION
Only a skilled technician is authorized to modify the settings on the Bypass menu
Batteries
Threshold values
Reserve Time
This sets the start time of the battery
autonomy warning [min]
MaxTime on Battery
This sets the maximum functioning time in
battery mode. Once this time has elapsed,
the UPS turns off. Set at OFF to disable the
function
Charger
Standby Charge
If enabled, it activates the battery charge
with the UPS off
Auto Restart
Restart Enable
This enables or disables the restart of the
UPS when the mains returns after the total
discharge of the batteries
Min. Autonomy
This sets the percentage charge value of the
batteries to be reached with the function of
standby charge in order to restart automati-
cally the UPS after a total battery discharge.
Total KB
This sets the total number of KB installed. The parameter is necessary
for the UPS to provide correct values for the autonomy based on the
load applied and for a correct battery charge.
Capacity (*)
This sets the capacity value of the batteries in the UPS [Ah].
(*) Only available in “Service Mode”
CAUTION
Only a skilled technician is authorized to modify the settings on the Batteries menu