![LEGRAND Trimod HE Скачать руководство пользователя страница 34](http://html.mh-extra.com/html/legrand/trimod-he/trimod-he_user-manual_1872201034.webp)
34
6.
Diagnosis
6.1
Luminous and audible notifications
The status indicator on the front panel of the UPS and the led on the front of every power module change their colour
according to the actual functioning status of the UPS or of the individual power module in accordance with the table
shown below.
INDICATION
Some luminous notifications can be accompanied by an audible signal. To turn off the audible notification, press the ESC
key. On every subsequent press, the notification is silenced or enabled.
INDICATION
If it is not possible to solve the problem, contact the LEGRAND Technical Support Service.
STATUS
INDICATOR
POWER MODULE
LED
AUDIBLE
NOTIFICATION
STATUS
MESSAGE
UPS STATUS DESCRIPTION AND
OPERATING ADVICE
GREEN
Steady
GREEN
Steady
-
TRIMOD
Normal functioning with mains
present and load within the limits
-
-
-
3V Battery Fail
Contact the LEGRAND Technical
Support Service
GREEN
Steady
ORANGE
Flashing
ORANGE
Flashing
-
Out/phase
turned OFF
Phase off in configuration of 3
independent phases output.
Check the output setup.
GREEN
Steady
ORANGE
Flashing
-
-
Modules
turned off
Command board in hot-swap
GREEN
Steady
1 module:
ORANGE
Steady
Remaining modules:
GREEN
Steady
-
Equalizing
Battery
Battery Equalization
in progress
GREEN
Quick flashing
GREEN
Quick flashing
-
-
Mains supply is absent on at least
one power module and/or the
frequency of the mains is not
correct (>68Hz or <43Hz) and/or
the input PLL is not synchronised.
A skilled technician must
check the mains.
GREEN
Quick flashing
-
-
-
One or more of the following
problems are present: bypass
absent, input PLL not
synchronised, bypass voltage
outside the limits, bypass sequence
not correct or reversed, bypass
frequency out of tolerance.
A skilled technician must
check the bypass line.
GREEN
Quick flashing
GREEN
Quick flashing
-
Bypass line KO
The bypass line cannot be used to
power the load
ORANGE
Quick flashing
ORANGE
Flashing
-
Forced on Bypass
UPS on Bypass
Operation in
forced bypass mode
ORANGE
Steady
ORANGE
Steady
500 ms on and
12 s off
UPS on Battery
Stored energy mode
ORANGE
Steady
ORANGE
Steady
-
Battery Cal...
Battery calibration
in progress
ORANGE
Steady
-
-
Battery Test...
Battery test in progress
continues...
Содержание Trimod HE
Страница 1: ...Trimod HE User manual Item LE11916AA 11 19 01 CT ...
Страница 2: ...2 EN ENGLISH 3 Trimod HE ...
Страница 54: ...54 ...