KEOR T EVO
Installa
tion & Oper
ation M
anual
Description of the Symbols Used in the Manual
This symbol points out the instructions which are especially important.
This symbol points out the risk of electric shock if the following instruction is
not followed.
This symbol points out the instructions, which may result with injury of the
operator or damage of the equipment if not followed.
All packing material must be recycled in compliance with the laws in force in the
country where the system is installed.
Description of the Symbols Used in the Manual
UPS: Uninterruptible Power Supply
ESD: Emergency Switching Device
RS232: Serial Communication Protocol
RS485: Serial Communication Protocol
MODBUS: Modicon Communication Protocol
SNMP: Simple Network Management Protocol
V: Volt
A: Ampere
P: Power
For Mains Supply, Auxiliary Mains Supply, Output, Battery Circuit Breaker and Maintenance Bypass Circuit
Breaker;
“ON”: Closing the Circuit
“OFF”: Opening the Circuit
KEOR T EVO
Installa
tion & Oper
ation M
anual
Description of the Symbols Used in the Manual
This symbol points out the instructions which are especially important.
This symbol points out the risk of electric shock if the following instruction is
not followed.
This symbol points out the instructions, which may result with injury of the
operator or damage of the equipment if not followed.
All packing material must be recycled in compliance with the laws in force in the
country where the system is installed.
Description of the Symbols Used in the Manual
UPS: Uninterruptible Power Supply
ESD: Emergency Switching Device
RS232: Serial Communication Protocol
RS485: Serial Communication Protocol
MODBUS: Modicon Communication Protocol
SNMP: Simple Network Management Protocol
V: Volt
A: Ampere
P: Power
For Mains Supply, Auxiliary Mains Supply, Output, Battery Circuit Breaker and Maintenance Bypass Circuit
Breaker;
“ON”: Closing the Circuit
“OFF”: Opening the Circuit
41
41
KEOR T EVO
Installa
tion & Oper
ation M
anual
6.3.1.7.
External Maintenance Bypass Connection
If External Maintenance Bypass would be used;
connect normally open auxiliary contact of External
Maintenance Bypass MCCB on the distribution panel
to terminals
a/X6
and
b/X6
on UPS.
6.3.1.8.
Backfeed Protection
for Single Input
Figure.6.3.1.8-1
Backfeed Protection Connection
for Single Input
Mains
X1
and
auxiliary
X4
have to be connected as shown in Figure 6.3.1.8-1.
The external device
(contactor)
is not part of the UPS, is provided and installed at
customer care.
In case of mains failure, contactor will isolate the UPS in order to protect the upstream distribution
circuits.
The installer shall apply the following warning label on all primary power isolator that supplies the
UPS.
External back feed protection device installation is necessary to prevent
hazardous voltage from being present on the UPS input AC distribution panel
after interruption of input AC power