KEOR T EVO
Installa
tion & Oper
ation M
anual
Description of the Symbols Used in the Manual
This symbol points out the instructions which are especially important.
This symbol points out the risk of electric shock if the following instruction is
not followed.
This symbol points out the instructions, which may result with injury of the
operator or damage of the equipment if not followed.
All packing material must be recycled in compliance with the laws in force in the
country where the system is installed.
Description of the Symbols Used in the Manual
UPS: Uninterruptible Power Supply
ESD: Emergency Switching Device
RS232: Serial Communication Protocol
RS485: Serial Communication Protocol
MODBUS: Modicon Communication Protocol
SNMP: Simple Network Management Protocol
V: Volt
A: Ampere
P: Power
For Mains Supply, Auxiliary Mains Supply, Output, Battery Circuit Breaker and Maintenance Bypass Circuit
Breaker;
“ON”: Closing the Circuit
“OFF”: Opening the Circuit
KEOR T EVO
Installa
tion & Oper
ation M
anual
Description of the Symbols Used in the Manual
This symbol points out the instructions which are especially important.
This symbol points out the risk of electric shock if the following instruction is
not followed.
This symbol points out the instructions, which may result with injury of the
operator or damage of the equipment if not followed.
All packing material must be recycled in compliance with the laws in force in the
country where the system is installed.
Description of the Symbols Used in the Manual
UPS: Uninterruptible Power Supply
ESD: Emergency Switching Device
RS232: Serial Communication Protocol
RS485: Serial Communication Protocol
MODBUS: Modicon Communication Protocol
SNMP: Simple Network Management Protocol
V: Volt
A: Ampere
P: Power
For Mains Supply, Auxiliary Mains Supply, Output, Battery Circuit Breaker and Maintenance Bypass Circuit
Breaker;
“ON”: Closing the Circuit
“OFF”: Opening the Circuit
31
31
KEOR T EVO
Installa
tion & Oper
ation M
anual
Connect the phase cables to
X4
AUXILIARY SUPPLY: X4/L1 - X4/L2 - X4/L3
terminals, the neutral to
X4
AUXILIARY SUPPLY: X4/N
terminal.
Cables must be protected by fuses or MCCB, refer to Section 5.4
If auxiliary supply exists, remove all phase bridges
.
If the batteries are already built-in inside the UPS cabinet; in order to avoid any danger during
transportation, some battery connections are left unconnected.
Thus, remove the left & right covers of UPS; disconnect the side panels’ earth cables.
Connect the unconnected battery cables to the related battery connectors. The unconnected cables
are labelled. You may find detailed information about battery connection as follows.
There i
s no need for any further connection,
c
o
n
nect the side panels’ earth cables and replace the
covers.
Internal Battery Connection:
6.3.1.4.
Battery Connection
You ma
y find mor
e information about KEOR T EVO Models and Battery capacity in Section 6.1. Models and
Dimensions.
Battery fast fuses shall only be replaced with fuses of the same type and rating.
If UPS with internal battery; there are no
X5
and
X8
terminals mounted on the UPS.
Danger of e
xplosion and fir
e if the batteries of the wrong type are used.
Do not use internal and external battery together!
LETHAL VOLTAGE
of nominal 720 VDC is present when the external battery
connections are made.
The batteries must be charged min. 10 hours befor
e first
-use.