6 - Main menu
One of the following options can be selected
for each actuator in the list:
Load managed by just one contact (e.g.: thermostatic valve)
Load managed by two interlocked relays (e.g. motor-driven
valve with opening contact and closing contact)
Fan-coil with control of one valve and selector switch up to 3
speeds
Interface for Climaveneta Fan-coil
Press the
key to send the configuration set
to the zone
09:
Not connected
H:
ON/OFF
C:
OPEN/CLOSE
FAN–COIL 3V
Zone test . . .
Configuration
invalid
ERROR
Verify the
probe
configuration
FAN–COIL 3V
The control unit tests the configuration.
When this is finished there may be two error
messages:
Trying to set a configuration of actuators which is
not allowed (example: actuators of different type
for the same function) in a probe
Check that the probe is in standard configuration
(MOD=CEN) and try again; if it is not this type of
configuration, the control unit cannot configure
the probe.
Zone state
Current profiles
Programming
Setup
Mode
FAN–COIL 3V
GATEWAY
ON/OFF
OPEN/CLOSE
01:
Living room
02:
Zone2
03: Zone3
Pumps