Detector switch - Dual Tech

SCS

Technical data sheet: S000077070EN-1 

Updated:  

Created: 17/12/2012

  1. Use

This device allows a light source to be controlled automatically through 

the detection of any presence in the surveillance zone using local 

controls.

Presence sensor with 180° detection angle.

Detection type: infrared (PIR) and ultrasound (US) 

Assembly type: wall flush mounted

  2. Technical feaTUres

Voltage: 27 V

=

No-load power consumption: 20 mA

Connection between the sensor and controller: BUS/SCS cable 

Wiring: 2 x 0.35 mm

2

Flush-mounting box: 40 mm min.

Weight: 60 g

Impact resistance: IK04

Penetration by solid and liquid matter: IP20

Usage temperature: - 5°C to + 45°C

Storage temperature: - 20°C to + 70°C 

Type of terminals:  screw

conTenTs Page

1. Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

2. Technical characteristics. . . . . . . . . . . . . . . . .1

3. Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

4. Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

5. Installation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

6. Operation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

7. Settings  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

8. Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . .3

9. Performance. . . . . . . . . . . . . . . . . . . . . . . . . . . .4

10. Care  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

11. Standards and approvals . . . . . . . . . . . . . . . .5

12. Troubleshooting  . . . . . . . . . . . . . . . . . . . . . . . .5

LEARN 

button

LED

LED 

detection

ON - OFF button

PIR Detector /  

Sensor

Light level 

cell

US Detector / 

Sensor

US Detector / 

Sensor

0 672 26

0 784 86

5 740 48 

5 740 98

  3. Dimensions

45

45

51

35

  4. connecTion

Pressing the auxiliary control allows the load to be switched on or off 

manually. If the control is not pressed, the sensor will cut off the load 

at the end of the time delay or when the light level threshold has been 

reached.

BUS/SCS

Содержание 0 672 26

Страница 1: ...60 g Impact resistance IK04 Penetration by solid and liquid matter IP20 Usage temperature 5 C to 45 C Storage temperature 20 C to 70 C Type of terminals screw Contents Page 1 Use 1 2 Technical characteristics 1 3 Dimensions 1 4 Connection 1 5 Installation 2 6 Operation 2 7 Settings 2 8 Configuration 3 9 Performance 4 10 Care 5 11 Standards and approvals 5 12 Troubleshooting 5 LEARN button LED LED ...

Страница 2: ...l detection the product will cut off the load after 3 minutes If another presence is detected in the 3 minutes following initial detection the device will cut off the load at the end of the set time delay Manual on Auto off mode Comes on via a manual switch automatic switch off Where no presence is detected and at the end of the time delay set After switch off any new detection within a 30 second ...

Страница 3: ...2 35 Light level threshold 500 lux 20 100 300 500 1000 lux 0 1275 lux Advanced mode Calibration 0 99995 lux Regulation Inactive Activate Deactivate Light contribution Auto Auto 1275 lux 7 Settings continued 7 3 Modifying the parameters using the configuration tools 0 882 35 Simplified configuration tool 0 882 30 Advanced configuration tool When the sensor receives an IR command using the configura...

Страница 4: ...or s sensitivity The sensor s sensitivity can be adjusted using the S configurator If the sensor is a Dual Tech then the sensitivity selected is applied to all technologies S configurator Sensitivity of the sensor No configurator Low 1 Medium 2 High 3 Very High The T configurator time delay Time that the load is switched ON T configurator Time Delay in min No configurator 15 1 0 5 2 1 3 2 4 5 5 10...

Страница 5: ...indow Decrease the power of the luminaires Lighting switches off when there are people present and the natural light level is not adequate darkness Time delay too short Detection sensitivity too low Light level threshold too low Increase the time delay 10 to 1 minutes is recommended for work areas Increase the sensitivity Move the sensor closer to the work area Increase the threshold 10 Care Keep ...

Отзывы: