2/5
Catalogue number(s): 0 672 26 - 0 784 86 - 5 740 48/98
Detector switch - Dual tech
sCs
Technical data sheet: S000077070EN-1
Updated:
Created: 17/12/2012
5. insTallaTion
5.1 sensor positioning
PIR
US
5.2 recommended light exposure
5.3 Positioning
2.5 m
1 m
2.5 m
(
*
)
(
*
)
(
*
)
Not supplied
6. oPeraTion
6.1 more than one sensor and more than one load
manual on/automatic off mode
Pressing the auxiliary control allows the load to be switched on or off
manually. If the control is not pressed, the sensor will cut off the load
at the end of the time delay or when the light level threshold has been
reached.
auto on/off mode:
The load will be switched on and off automatically.
option: It is possible to control the sensor by infrared remote control
using: Cat. Nos. 0 882 00/01/20/31/32/33.
1
2
7. seTTings
7.1 Detection parameters
Time delay: Length of time the load is on after detection.
sensitivity: Detection range setting.
modes:
auto on/auto off mode:
Comes on automatically:
- At the detection of a presence if there is an insufficient natural level of
light.
Turns off automatically:
- If no presence is detected and at the end of the time delay set.
- Or if the natural light level is sufficient (regulation activated)
Another detection causes automatic switch-on if there is insufficient
light.
Walk-through mode:
- If no presence is detected in the 20 seconds following an initial
detection, the product will cut off the load after 3 minutes.
- If another presence is detected in the 3 minutes following initial
detection, the device will cut off the load at the end of the set time
delay.
manual on/auto off mode:
Comes on via a manual switch, automatic switch off:
- Where no presence is detected and at the end of the time delay set.
After switch-off, any new detection within a 30 second period triggers
an automatic switch-on. The Restart function must be activated.
After 30 seconds the device is switched on via a manual switch.
Partial on/group off mode:
Possibility of controlling one or more lighting points individually.
In this mode it is essential for a lighting group to be created:
- either by manual teach phase.
- or from the advanced configuration tool Cat. No. 882 30 using the
function "PnL capteur" (PnL sensor).
The sensor switches on the loads that are linked to it via the actuator.
Where there is no detection and at the end of the time delay it switches
off all loads in the group to which it belongs.
sensor parameters
Default
value
modifiable
parameters
configuration
tools
0 882 30 0 882 35
Time delay
15 mins
3, 5, 10, 15,
20 min
−
30s - 255 h
59 min 59s
−
sensitivity
PIR
(very high)
Low, medium,
high, very high
m
odes
auto on/auto off
Inactive
Activate/
Deactivate
Walk-through
mode
Active
Activate/
Deactivate
manual on/auto
off
Inactive
Activate/
Deactivate
Partial on/
group off
Inactive
Activate/
Deactivate
−
Detection system
initial
PIR
Not modifiable
−
maintain
PIR
Not modifiable
−
restart
PIR
PIR, Deactivate
−
alarm
Inactive
Activate/
Deactivate
−