LEGRAND 0 672 26 Скачать руководство пользователя страница 2

2/5

Contents

Catalogue number(s): 0 672 26 - 0 784 86 -  5 740 48/98

Detector switch - Dual tech

sCs

Technical data sheet: S000077070EN-1 

Updated:  

Created: 17/12/2012

  5. insTallaTion

5.1   sensor positioning

PIR

US

5.2   recommended light exposure

5.3   Positioning

2.5 m

1 m

2.5 m

(

*

)

(

*

)

(

*

)

 Not supplied

  6. oPeraTion

6.1   more than one sensor and more than one load

manual on/automatic off mode  

Pressing the auxiliary control allows the load to be switched on or off 

manually. If the control is not pressed, the sensor will cut off the load 

at the end of the time delay or when the light level threshold has been 

reached.

auto on/off mode:  

The load will be switched on and off automatically.
option:  It is possible to control the sensor by infrared remote control 

using: Cat. Nos. 0 882 00/01/20/31/32/33.

1

2

  7. seTTings

7.1   Detection parameters

   Time  delay: Length of time the load is on after detection. 

 sensitivity: Detection range setting.

modes:

 auto on/auto off mode: 

Comes on automatically: 

-  At the detection of a presence if there is an insufficient natural level of 

light.

Turns off automatically: 

- If no presence is detected and at the end of the time delay set. 

- Or if the natural light level is sufficient (regulation activated)

Another detection causes automatic switch-on if there is insufficient 

light.

 Walk-through mode:

-   If no presence is detected in the 20 seconds following an initial 

detection, the product will cut off the load after 3 minutes.

-  If another presence is detected in the 3 minutes following initial 

detection, the device will cut off the load at the end of the set time 

delay.

 manual on/auto off mode: 

Comes on via a manual switch, automatic switch off: 

-  Where no presence is detected and at the end of the time delay set.
After switch-off, any new detection within a 30 second period triggers 

an automatic switch-on. The Restart function must be activated.

After 30 seconds the device is switched on via a manual switch.
Partial on/group off mode:

Possibility of controlling one or more lighting points individually.

In this mode it is essential for a lighting group to be created:

- either by manual teach phase.

- or from the advanced configuration tool Cat. No. 882 30 using the 

function "PnL capteur" (PnL sensor).

The sensor switches on the loads that are linked to it via the actuator. 

Where there is no detection and at the end of the time delay it switches 

off all loads in the group to which it belongs.

sensor parameters

Default 

value

modifiable  

parameters

configuration  

tools

0 882 30 0 882 35

Time delay

15 mins

3, 5, 10, 15, 

20 min

30s - 255 h 

59 min 59s

sensitivity

PIR  

(very high)

 

Low, medium, 

high, very high

m

odes

auto on/auto off

Inactive

Activate/

Deactivate

Walk-through 

mode

Active

Activate/

Deactivate

manual on/auto 

off

Inactive

Activate/

Deactivate

Partial on/ 

group off

Inactive

Activate/

Deactivate

Detection  system

initial

PIR

Not modifiable

maintain

PIR

Not modifiable

restart

PIR

PIR, Deactivate

alarm

Inactive

Activate/

Deactivate

Содержание 0 672 26

Страница 1: ...60 g Impact resistance IK04 Penetration by solid and liquid matter IP20 Usage temperature 5 C to 45 C Storage temperature 20 C to 70 C Type of terminals screw Contents Page 1 Use 1 2 Technical characteristics 1 3 Dimensions 1 4 Connection 1 5 Installation 2 6 Operation 2 7 Settings 2 8 Configuration 3 9 Performance 4 10 Care 5 11 Standards and approvals 5 12 Troubleshooting 5 LEARN button LED LED ...

Страница 2: ...l detection the product will cut off the load after 3 minutes If another presence is detected in the 3 minutes following initial detection the device will cut off the load at the end of the set time delay Manual on Auto off mode Comes on via a manual switch automatic switch off Where no presence is detected and at the end of the time delay set After switch off any new detection within a 30 second ...

Страница 3: ...2 35 Light level threshold 500 lux 20 100 300 500 1000 lux 0 1275 lux Advanced mode Calibration 0 99995 lux Regulation Inactive Activate Deactivate Light contribution Auto Auto 1275 lux 7 Settings continued 7 3 Modifying the parameters using the configuration tools 0 882 35 Simplified configuration tool 0 882 30 Advanced configuration tool When the sensor receives an IR command using the configura...

Страница 4: ...or s sensitivity The sensor s sensitivity can be adjusted using the S configurator If the sensor is a Dual Tech then the sensitivity selected is applied to all technologies S configurator Sensitivity of the sensor No configurator Low 1 Medium 2 High 3 Very High The T configurator time delay Time that the load is switched ON T configurator Time Delay in min No configurator 15 1 0 5 2 1 3 2 4 5 5 10...

Страница 5: ...indow Decrease the power of the luminaires Lighting switches off when there are people present and the natural light level is not adequate darkness Time delay too short Detection sensitivity too low Light level threshold too low Increase the time delay 10 to 1 minutes is recommended for work areas Increase the sensitivity Move the sensor closer to the work area Increase the threshold 10 Care Keep ...

Отзывы: