LEGRAND 0 672 26 Скачать руководство пользователя страница 5

5/5

Contents

Catalogue number(s): 0 672 26 - 0 784 86 -  5 740 48/98

Detector switch - Dual tech

sCs

Technical data sheet: S000077070EN-1 

Updated:  

Created: 17/12/2012

ProBlem

caUses

solUTions

Lighting stays on when there is no-one present

Sources of interference can cause false tripping, 

such as: air current, vibrations, radiators

1-  Reduce the sensitivity level
2-  If the interference continues: using the 

configuration tool, go into the Detection 

system parameters, select Maintain and then 

choose PIR and US

3-  If the interference still continues, move the 

sensor away from sources of interference

Lighting does not switch off during the day 

when there is an adequate level of natural light

Regulation function not active
Light level threshold set too high
Light contribution is too high

Activate the regulation function
Reduce the light level threshold
Check that the sensor is positioned correctly in 

relation to the window
Decrease the power of the luminaires

Lighting switches off when there are people 

present and the natural light level is not 

adequate (darkness)

Time delay too short
Detection sensitivity too low
Light level threshold too low

Increase the time delay
10 to 1 minutes is recommended for work areas
Increase the sensitivity
Move the sensor closer to the work area
Increase the threshold

  10. care

Keep the lens clean.

Clean the surface with a cloth.

Do not use acetone, tar-removing cleaning agents or trichloroethylene.

Resistant to the following products:  - Hexane (EN 60669-1) 

- Methylated spirit 

- Soapy water 

- Diluted ammonia 

- Bleach diluted to 10% 

- Window-cleaning products. 

caution: 

Always test before using other special cleaning products.

  11. sTanDarDs

Directive: CE
Installation standards: NFC 15-100
Product standards: IEC 60669-2-1
Environmental standards: 

-  European Directive 2002/96/EC: 

WEEE (Waste Electrical and Electronic Equipment).

-  European Directive 2002/95/EC: 

RoHS (Restriction of Hazardous Substances).

- Decrees and/or regulations:  ERP (public buildings) 

ERT (workplace buildings) 

IGH (high-rise buildings)

  12. TroUBleshooTing

Содержание 0 672 26

Страница 1: ...60 g Impact resistance IK04 Penetration by solid and liquid matter IP20 Usage temperature 5 C to 45 C Storage temperature 20 C to 70 C Type of terminals screw Contents Page 1 Use 1 2 Technical characteristics 1 3 Dimensions 1 4 Connection 1 5 Installation 2 6 Operation 2 7 Settings 2 8 Configuration 3 9 Performance 4 10 Care 5 11 Standards and approvals 5 12 Troubleshooting 5 LEARN button LED LED ...

Страница 2: ...l detection the product will cut off the load after 3 minutes If another presence is detected in the 3 minutes following initial detection the device will cut off the load at the end of the set time delay Manual on Auto off mode Comes on via a manual switch automatic switch off Where no presence is detected and at the end of the time delay set After switch off any new detection within a 30 second ...

Страница 3: ...2 35 Light level threshold 500 lux 20 100 300 500 1000 lux 0 1275 lux Advanced mode Calibration 0 99995 lux Regulation Inactive Activate Deactivate Light contribution Auto Auto 1275 lux 7 Settings continued 7 3 Modifying the parameters using the configuration tools 0 882 35 Simplified configuration tool 0 882 30 Advanced configuration tool When the sensor receives an IR command using the configura...

Страница 4: ...or s sensitivity The sensor s sensitivity can be adjusted using the S configurator If the sensor is a Dual Tech then the sensitivity selected is applied to all technologies S configurator Sensitivity of the sensor No configurator Low 1 Medium 2 High 3 Very High The T configurator time delay Time that the load is switched ON T configurator Time Delay in min No configurator 15 1 0 5 2 1 3 2 4 5 5 10...

Страница 5: ...indow Decrease the power of the luminaires Lighting switches off when there are people present and the natural light level is not adequate darkness Time delay too short Detection sensitivity too low Light level threshold too low Increase the time delay 10 to 1 minutes is recommended for work areas Increase the sensitivity Move the sensor closer to the work area Increase the threshold 10 Care Keep ...

Отзывы: