Detector switch - Dual tech

sCs

Technical data sheet: S000077070EN-1 

Updated:  

Created: 17/12/2012

   7.  seTTings (continued)

 7.1 Detection parameters (continued)
Detection system:
initial detection:
 The load is switched on as soon as the first detection 

occurs if the natural light level is below the light level threshold.
maintain: The load remains active if another presence is detected.
restart: In manual mode. After switch-off, any new detection within a 

30 second period triggers an automatic switch-on.

After 30 seconds the device must be switched on manually. 

alarm: an audible signal is emitted before switch-off. (1 minute before, 

then 30 seconds, then 10 seconds).

7.2  light parameters

  light level threshold: Value at which the load comes on if the 

natural light level is less than the setting.

caution: 

The device becomes a motion detector at 1275 lux.

advanced mode:

   calibration: The surrounding light level measured with a luxmeter 

must then be transmitted to the sensor (see data sheet  

Cat. No. 0 882 30)

.

   regulation: Automatic switch-off of the load 10 minutes after 

the light level threshold is exceeded with an additional safety 

threshold (to avoid lights switching off at the wrong moment).

light contribution: Quantity of additional lux provided by the load 

being switched on.  

When the light contribution parameter is set to "Auto" (value 0) on the 

configuration tool Cat. No. 0 882 30 the sensor automatically calculates 

the light contribution.

sensor parameter

Default 

value

modifiable  

parameters

configuration  

tools

0 882 30 0 882 35

light level threshold

500 lux

20, 100, 300, 500, 

1000 lux

0 - 1275 lux

a

dv

anc

ed 

mo

de

calibration

0 - 99995 lux

regulation

Inactive

Activate/

Deactivate

light 

contribution

Auto

Auto - 1275 lux

   7.  seTTings (continued)

7.3  modifying the parameters using the configuration tools

• 0 882 35: Simplified configuration tool

 

• 0 882 30: Advanced configuration tool

When the sensor receives an IR command using the configuration tool  

it emits a beep acknowledging the modification.

For more information about setting parameters, refer to the data sheet 

for the configuration tool Cat. No. 0 882 30.
Range: 1 m.
-  restore to factory settings:

1

st

 press: Short press on LEARN: the LED flashes slowly.

2

nd

 press:  Press and hold down LEARN for 10 seconds until the LED 

flashes quickly.

  8. configUraTion 

8.1   Physical configuration

BUs scs sensor Physical configuration

The physical configuration only authorises point-to-point addressing: 

one single actuator can be controlled via the sensor.

a: Area (0 –A)

Pl: Light point (0 – F)

m: Mode (0 – 4)

s: Sensitivity of the motion detector (0 – 3)

T: Time delay (0 – 9)

D: Light level threshold or daylight set point (0 – 5)

The a and Pl configurator: addressing

The A and PL configurators provide the address of the actuator to be 

controlled.

nB: 

-  If the product does not have the A and PL configurators positioned 

then it is not configured.

- The configuration A=0 and PL=0 does not exist

The m configurator: the modes

The M configurator allows the user to choose the product's modes of 

operation:
m

 

configurator

mode

No configurator

Automatic On/Off mode & without setting 

range & with presence detection

1

Automatic On/Off mode & light level measure 

& without presence detection

2

Supervision mode

3

Automatic On/Off mode & setting range & 

with detection

4

Automatic On/Off mode & setting range & 

without detection

Содержание 0 672 26

Страница 1: ...60 g Impact resistance IK04 Penetration by solid and liquid matter IP20 Usage temperature 5 C to 45 C Storage temperature 20 C to 70 C Type of terminals screw Contents Page 1 Use 1 2 Technical characteristics 1 3 Dimensions 1 4 Connection 1 5 Installation 2 6 Operation 2 7 Settings 2 8 Configuration 3 9 Performance 4 10 Care 5 11 Standards and approvals 5 12 Troubleshooting 5 LEARN button LED LED ...

Страница 2: ...l detection the product will cut off the load after 3 minutes If another presence is detected in the 3 minutes following initial detection the device will cut off the load at the end of the set time delay Manual on Auto off mode Comes on via a manual switch automatic switch off Where no presence is detected and at the end of the time delay set After switch off any new detection within a 30 second ...

Страница 3: ...2 35 Light level threshold 500 lux 20 100 300 500 1000 lux 0 1275 lux Advanced mode Calibration 0 99995 lux Regulation Inactive Activate Deactivate Light contribution Auto Auto 1275 lux 7 Settings continued 7 3 Modifying the parameters using the configuration tools 0 882 35 Simplified configuration tool 0 882 30 Advanced configuration tool When the sensor receives an IR command using the configura...

Страница 4: ...or s sensitivity The sensor s sensitivity can be adjusted using the S configurator If the sensor is a Dual Tech then the sensitivity selected is applied to all technologies S configurator Sensitivity of the sensor No configurator Low 1 Medium 2 High 3 Very High The T configurator time delay Time that the load is switched ON T configurator Time Delay in min No configurator 15 1 0 5 2 1 3 2 4 5 5 10...

Страница 5: ...indow Decrease the power of the luminaires Lighting switches off when there are people present and the natural light level is not adequate darkness Time delay too short Detection sensitivity too low Light level threshold too low Increase the time delay 10 to 1 minutes is recommended for work areas Increase the sensitivity Move the sensor closer to the work area Increase the threshold 10 Care Keep ...

Отзывы: