17
WORKSHOP SPECIFICATIONS
XL³ 160
Cabinets in the XL
3
160 range are not designed to be joined together, but can be
combined vertically fairly simply.
Set of 2 joined
cabinets, with
meter and
incoming circuit
breaker at the
supply end
Mark the cutting limits on the side panels of the cabinets to be joined together, and
mark where the 4 holes are to be drilled.
Use the terminal block supports as marking
guides.
Drill both sides at the same time
(Ø 6.5 mm)
Cut the side panels to make the opening for
inserting the wiring.
After refit the drilled and cut side panels, place
the 4 screws and 4 M6 nuts in position, but do
not tighten them fully.
VERTICAL JOINING
1
MOUNTING
WWW.LEGRAND.COM