LEGRAND 0 026 72 Скачать руководство пользователя страница 8

8/29

Technical data sheet: S000114123EN-1 

Updated: 

Created: 18/01/2021

Cat. No(s): 0 026 72/73/74/76/78/79

KNX controller multi-application DIN

   7 .  COMMUNICATION OBJECTS (continued)

7 .2 "General” parameter

Enable manual operation

  disable

*enable

This parameter can be used to enable/disable manual control. If 

manual operation is enabled, connected load can be controlled via 

the corresponding channel button on the device.

• Set the parameter to “

enable

This selection is used to enable manual operation.

•  Set the parameter to “

disable

This selection is used to disable manual operation.

Reset manual operation to KNX operation

*via push button

  automatically and via push button

This parameter determines how long manual operation remains 

activated.

Time for automatic reset 

in s[10…6000]

10…

*300

…6000

Manual operation remains activated until the adjusted time is up or 

deactivated by button manually.

Device alive operation active

*no

  yes

This object is used to report that device is still alive and connected to 

KNX line. (Heartbeat) If alive telegram is not received, device may be 

defective or KNX cable can be disconnected. If parameter is selected 

"

yes

", following parameters come up.

In operation bit

 

 0

*1

Telegram value can be selected as “1” or “0”.

In operation send interval

1…

*300

…65535

Telegram value is sent cyclically according to time interval.

Transmission delay [2…255s] after bus 

voltage return

*2

…255

The parameter defines the behaviour of the actuator at a bus power 

return. The transmission delay time determines the period between 

bus voltage recovery and the point after which telegrams can be sent.

Telegram limit active 

  no

*yes

Telegrams which are sent by the gateway can be limited with this 

parameter. If “yes” is selected, following parameters come up.

Telegram limit period

50ms…

*10s

…1dk

The limit period can be selected via telegram limit period parameter.

Max . number of transmitted telegram

1…

*20

…255

Maximum number of telegrams can be sent freely within a period.

Note:

If the value of the object cannot be sent in the time of a period. The 

object is buffered for the next period time. The buffered object will 

be updated if the object value is updated.

   7 .  COMMUNICATION OBJECTS (continued)

7 .2 "General” parameter (continued)

Activate scene

*yes

  no

If parameter is selected “

yes

”, “Scenes” section will be visible in 

parameter titles.

Weather alarm function

  enable

*

disable

If the parameter is selected “yes”, “Weather Alarm” section will be 

visible in parameter titles. You can find weather alarm information 

under the “Weather Alarm” section.

7 .3 "Weather alarms" parameter

Order of priority for weather alarms

*1 .Wind 2 .Rain 3 .Frost

  1.Wind 2.Frost 3.Rain

  1.Rain 2.Wind 3.Frost

  1.Rain 2.Frost 3.Wind

  1.Frost 2.Wind 3.Rain

  1.Frost 2.Rain 3.Wind

If an alarm is triggered, the drives move into a safe position and stay in 

safe position until the event is over. You can select the priority of the 

weather alarm. This parameter is applied for all blind/shutter channels 

which are enabled for weather protection function. If more than 

one weather alarms occur simultaneously, then only the alarm with 

highest priority will be activated. The other lower priority alarms are 

carried out after highest priority alarm is completed.

Wind alarm

*disable

  

enable

This parameter activates the wind alarm. If the parameter selected 

“enable”, “Monitoring period for wind alarm in s [0…1000]” parameter 

will be visible.

Monitoring period for wind alarm in s

[0…1000]

*0

…1000

The telegram of the active weather station is monitored cyclically. The 

actuator waits for a telegram from the weather station within the cycle 

time. If the telegram is not received within this monitoring period 

time, actuator assumes that the weather station is broken or bus line is 

damaged and the blind moves into the parameterized position.

0

: If “

0

” is selected cyclically monitoring is deactivated. If the alarm 

telegram value is “

1

”, weather alarm is activated.

Rain alarm

*disable

  

enable

This parameter activates the rain alarm. If the parameter selected 

enable

”, “

Monitoring period for rain alarm in s [0…1000]

” 

parameter is visible.

CONTENTS

Содержание 0 026 72

Страница 1: ...ch Sensor parameter 10 7 5 2 a Switch Dim Sensor parameter 11 7 5 2 a Switch Dim Sensor parameter continued 11 7 5 3 a Blind Sensor parameter 11 7 5 4 a Value Forced Operation parameter 12 7 6 Enable...

Страница 2: ...n parameter 23 7 10 2 A B1 Status Message parameter 24 7 10 3 A B1 Automatic Operation parameter 25 7 10 4 A B1 Direct Mode parameter 25 7 11 Function Chart 26 7 12 Object Description 26 7 12 1 Genera...

Страница 3: ...ut x4 AC Blind x2 DC Blind x1 2 Point valve x2 3 point valve x2 Suitable for switching resistive capacitive and inductive loads as well as fluorescent lamp loads according to EN 60 669 A single switch...

Страница 4: ...4123EN 1 Updated Created 18 01 2021 Cat No s 0 026 72 73 74 76 78 79 KNX controller multi application DIN 4 CONNECTION 0 026 72 73 AC Motor D2 NA Fan1 Fan2 Fan3 4 CONNECTION continued 0 026 74 AC Moto...

Страница 5: ...ted 18 01 2021 Cat No s 0 026 72 73 74 76 78 79 KNX controller multi application DIN 4 CONNECTION continued 0 026 76 AC Motor AC Motor DC Motor F G DC Motor F G 4 CONNECTION continued 0 026 78 79 AC M...

Страница 6: ...S4 or higher Important A detailed information about parameter configuration can be found in Product Manual of device Installation and commissioning of device may only be implemented by trained electri...

Страница 7: ...100 1 bit CW 98 Output A1 Staircase lighting duration 7 007 2 byte CRW Output A Output A B Move to position height 0 255 5 001 1 byte CW Fan A B1 Switch speed 3 1 001 1 bit CW Control input Fault con...

Страница 8: ...e sent freely within a period Note If the value of the object cannot be sent in the time of a period The object is buffered for the next period time The buffered object will be updated if the object v...

Страница 9: ...valuate the transmitted scene address and switches the output to the stored scene value A scene is activated when it receives its scene number at the scene object The storing of the current channel va...

Страница 10: ...is distinction between short and long operation The contact type of the push button attached to the channel is adjusted here Cyclic transmission of object no switch OFF switch ON always This paramete...

Страница 11: ...operation STOP telegram sends at the end of operation Brightness change on every sent telegram 100 6 25 1 56 This parameter is only visible with the Dimming steps options This parameter is cyclically...

Страница 12: ...op command is sent such as STOP Lamella adj UP or STOP Lamella adj DOWN 1 Shutter MOVE UP STOP Lamella UP 2 Shutter MOVE DOWN STOP Lamella DOWN 2 button stepping On operation Stop lamella adjustment T...

Страница 13: ...n shutter blind DC fan coil valve control individually Both output group can be combined into one DC blind In DC blind operation the four relay contacts of the device can be used to control electrical...

Страница 14: ...bus voltage return Behavior bus voltage failure keep position open contact close contact When the bus voltage fails the device set the wanted switching state of the output The relay can be open close...

Страница 15: ...mber of pre warning and time for pre warning interval The warning function is for warning that the staircase lighting time run out and the lights are switched off soon In the warning lights short turn...

Страница 16: ...B General parameter continued Behavior after ETS programming or after ETS reset Behavior bus voltage failure no reaction up down stop position 1 2 3 4 approach position This parameter can be used to c...

Страница 17: ...e Trigger reference movement communication object is visible The reference movement is triggered via this communication object In long time slight inaccuracies can occur so the upper and lower end pos...

Страница 18: ...This function allows you set a height position or slat position directly using with communication object Enable communication objects Move to pos Height Move slat 0 255 no yes The communication Move t...

Страница 19: ...havior in case of rain alarm Behavior in case of frost alarm no reaction up down stop position 1 position 2 position 3 position 4 individual position When the alarm is activated the blind moves this p...

Страница 20: ...tion communication object is updated After the bus voltage return forced position function set to the parametrized position Set the parameter to no forced position active The forced operation is deact...

Страница 21: ...ING is deactivated Set the parameter to 1 When the telegram is received 1 HEATING operation is activated COOLING is deactivated Monitoring control valves yes no This parameter activate the thermostat...

Страница 22: ...vel time This time is maximum one minute Valve limitation yes no The limitation of the control value limits the height of the control value The limitation is activated when a value is chosen which is...

Страница 23: ...ons Thus initially the number of fan levels required for the connected devices can be defined The number of fan levels can be specified separately for each fan coil channel Controlling the fan levels...

Страница 24: ...ime has elapsed 7 COMMUNICATION OBJECTS continued 7 10 Fan Coil parameter continued 7 10 2 A B1 Status Message parameter Enable communication object Status fan speed x 1 bit yes no The data format for...

Страница 25: ...peed In s 0 65535 0 65535 This parameter defines the dwell time for a fan speed of the fan until it switches to the next higher or lower fan speed 0 no delay time for switching 7 COMMUNICATION OBJECTS...

Страница 26: ...x Des 1 0x00 0 0x80 128 2 0x01 1 0x81 129 3 0x02 2 0x82 130 4 0x03 3 0x83 131 5 0x04 4 0x84 132 6 0x05 5 0x85 133 7 0x06 6 0x86 134 8 0x07 7 0x87 135 9 0x08 8 0x88 136 10 0x09 9 0x89 137 11 0x0A 10 0x...

Страница 27: ...d operation 1 byte 0 255 DPT 5 001 brightness value 2 byte 32768 32767 DPT 7 001 signed value 2 byte 0 65535 DPT 8 001 unsigned value 4 byte float value DPT14 068 temperature 4 byte 0 4294967295 DPT12...

Страница 28: ...or 4 104 Trigger reference movement Output A DTP 1 008 1 bit CW This object is triggered the reference movement If the telegram is received the blind is moved up or down end position Then the blind c...

Страница 29: ...OMMUNICATION OBJECTS continued 7 17 Fan Object Description No Object name Name DTP Type Length Flags 95 Fan speed switch Fan DPT 5 010 1 byte CW This object is used to switch on fan speed via 1 byte o...