Technical data sheet: S000114123EN-1
Updated:
Created: 18/01/2021
Cat. No(s): 0 026 72/73/74/76/78/79
KNX controller multi-application DIN
7 . COMMUNICATION OBJECTS (continued)
7 .2 "General” parameter
Enable manual operation
disable
*enable
This parameter can be used to enable/disable manual control. If
manual operation is enabled, connected load can be controlled via
the corresponding channel button on the device.
• Set the parameter to “
enable
”
This selection is used to enable manual operation.
• Set the parameter to “
disable
”
This selection is used to disable manual operation.
Reset manual operation to KNX operation
*via push button
automatically and via push button
This parameter determines how long manual operation remains
activated.
Time for automatic reset
in s[10…6000]
10…
*300
…6000
Manual operation remains activated until the adjusted time is up or
deactivated by button manually.
Device alive operation active
*no
yes
This object is used to report that device is still alive and connected to
KNX line. (Heartbeat) If alive telegram is not received, device may be
defective or KNX cable can be disconnected. If parameter is selected
"
yes
", following parameters come up.
In operation bit
0
*1
Telegram value can be selected as “1” or “0”.
In operation send interval
1…
*300
…65535
Telegram value is sent cyclically according to time interval.
Transmission delay [2…255s] after bus
voltage return
*2
…255
The parameter defines the behaviour of the actuator at a bus power
return. The transmission delay time determines the period between
bus voltage recovery and the point after which telegrams can be sent.
Telegram limit active
no
*yes
Telegrams which are sent by the gateway can be limited with this
parameter. If “yes” is selected, following parameters come up.
Telegram limit period
50ms…
*10s
…1dk
The limit period can be selected via telegram limit period parameter.
Max . number of transmitted telegram
1…
*20
…255
Maximum number of telegrams can be sent freely within a period.
Note:
If the value of the object cannot be sent in the time of a period. The
object is buffered for the next period time. The buffered object will
be updated if the object value is updated.
7 . COMMUNICATION OBJECTS (continued)
7 .2 "General” parameter (continued)
Activate scene
*yes
no
If parameter is selected “
yes
”, “Scenes” section will be visible in
parameter titles.
Weather alarm function
enable
*
disable
If the parameter is selected “yes”, “Weather Alarm” section will be
visible in parameter titles. You can find weather alarm information
under the “Weather Alarm” section.
7 .3 "Weather alarms" parameter
Order of priority for weather alarms
*1 .Wind 2 .Rain 3 .Frost
1.Wind 2.Frost 3.Rain
1.Rain 2.Wind 3.Frost
1.Rain 2.Frost 3.Wind
1.Frost 2.Wind 3.Rain
1.Frost 2.Rain 3.Wind
If an alarm is triggered, the drives move into a safe position and stay in
safe position until the event is over. You can select the priority of the
weather alarm. This parameter is applied for all blind/shutter channels
which are enabled for weather protection function. If more than
one weather alarms occur simultaneously, then only the alarm with
highest priority will be activated. The other lower priority alarms are
carried out after highest priority alarm is completed.
Wind alarm
*disable
enable
This parameter activates the wind alarm. If the parameter selected
“enable”, “Monitoring period for wind alarm in s [0…1000]” parameter
will be visible.
Monitoring period for wind alarm in s
[0…1000]
*0
…1000
The telegram of the active weather station is monitored cyclically. The
actuator waits for a telegram from the weather station within the cycle
time. If the telegram is not received within this monitoring period
time, actuator assumes that the weather station is broken or bus line is
damaged and the blind moves into the parameterized position.
0
: If “
0
” is selected cyclically monitoring is deactivated. If the alarm
telegram value is “
1
”, weather alarm is activated.
Rain alarm
*disable
enable
This parameter activates the rain alarm. If the parameter selected
“
enable
”, “
Monitoring period for rain alarm in s [0…1000]
”
parameter is visible.