![LEGRAND 0 026 72 Скачать руководство пользователя страница 15](http://html1.mh-extra.com/html/legrand/0-026-72/0-026-72_manual_1870844015.webp)
15/29
Technical data sheet: S000114123EN-1
Updated:
Created: 18/01/2021
Cat. No(s): 0 026 72/73/74/76/78/79
KNX controller multi-application DIN
7 . COMMUNICATION OBJECTS (continued)
7 .7 "Switch" parameter (continued)
7 .7 .2 "A1 - Function" parameter (continued)
7 .7 .2 .1 A1 - Function" parameter (continued)
Duration of staircase lighting [min]/ [sec]
0…
*5
…240[min]
*0
…59 [sec]
Staircase function on time is calculated by “
duration of staircase
lighting”
. Staircase lighting time is defined by this parameter. At
the end of the on time, the relay off or active the staircase warning
functions.
Staircase retrigger
*not retriggerable
yes retriggerable
up to staircase lighting time 2x
up to staircase lighting time 3x
up to staircase lighting time 4x
up to staircase lighting time 5x
This parameter defines whether the staircase on time can be retrigger
able or not so the on time can be extended by ‘Enable staircase
function’. You can repeat retrigger function until the repeater count
reached the maximum value (2x, 3x, 4x, 5x). If the parameter selects
"
not retriggerable
", staircase on time doesn’t extend.
Reaction to OFF telegram
*switch off
ignore
After this parameter selected "
switching off
", "
ignored
". Enable
staircase function’ communication object ‘disable’ command.
Staircase time can be changed by object
yes
*no
"
Staircase lighting duration
" communication object is visible if a
"
Staircase time can be changed by object
" parameter selects "
yes
"
This communication object is 2 byte. The value defines the staircase
on time in second.
NOTE: After a bus voltage fails, staircase on time returns default value
(Duration of staircase lighting).
Restart staircase after “Permanent ON”
yes
*no
If this parameter is selected "
yes
", receive "
Permanent ON
"
communication object after restart staircase function.
Activate pre-warning time?
yes
*no
The warning function can be activated by this parameter select "
yes
".
Then, you can adjust pre-warning time, number of pre-warning and
time for pre-warning interval. The warning function is for warning
that the staircase lighting time run out and the lights are switched
off soon. In the warning, lights short turn off. Switch status is ON until
finish warning time.
Pre-warning time Minutes (0…59)
Second (0…59)
*0…59
0…
*30
…59
How long the lights shall be switched on in the period.
Number of pre-warning (1…10)
1…
*2
…10
Enter the number of how many blink doing in the warning.
Time for pre-warning intervals
Seconds (0…59)
0…
*3
…59
How long the lights shall be switched off in the period.
Activate on delay
yes
*no
This parameter is used delay to switch off position before staircase
start.
7 . COMMUNICATION OBJECTS (continued)
7 .7 "Switch" parameter (continued)
7 .7 .2 "A1 - Function" parameter (continued)
7 .7 .2 .2 " A1 - External logic" parameter
Logic function can be used independently for each output. With this
function, the ‘Switch’ object can be logically linked with the "
External
logic input
". Channel relay switch a result of the logic operation. For
example, "
Switch
" object value 1 and "
External logic input
" object
value 0 relay switch as a result of 1 & 0 operation.
External logic function type
*AND
OR
XOR
This parameter selects the type of logic function between "
Switch
"
and "
External logic input
" objects.
Invert result
yes
*no
If you want to inverted logic function result, you should select "
yes
".
Logic object value after bus voltage return
“1”
*”0”
This parameter defines the value of the "
External logic input
" object
after bus voltage return.
Note:
The values of the "
External logic
" communication objects doesn’t
store at the bus voltage failure.
7 .7 .2 .3 "A1 - Sweep" parameter
Sweep function only starts to operate if the relay is switched ON. It’s an
alternative way for turning off the relay with pre-warning. The sweep
function is desired to warn a person that lights will go out shortly.
Send counter value
1…
*3
…10
The lamps connected to the relay will be switched off as many times.
Enter the number of how many blink doing in the warning.
Blink on time
0,5sec…
*1sec
…5sec
How long the lights shall be switched on in the period.
CONTENTS