GSM SMS Alarm Messenger
SMSPro (Version 7)
33
COMMAND (Analog to Digital Channel)
11.23)
AD Parameters Setup
PWD:XXXX,ADVALE
B
:UUUUU,XXXXX,NNNNN,
Y
,ZZZZZ,WWWWW%
B
Channel 1 or 2
UUUUU
Measuring Range Upper Limit
XXXXX
Measuring Range Lower Limit
NNNNN Start
Value
Y
0: AD Alarm disabled
1: AD Alarm enabled, Relay On Time Lapse
2: AD alarm enabled, Relay On when AD is higher than Alert High
Relay Off when AD resumes normal
3: AD alarm enabled, Relay On when AD is lower than Alert Low
Relay Off when AD resumes normal
4: AD alarm enabled, Relay On when AD is beyond Alert High & Low
Relay Off when AD is within Alert High & Low
ZZZZZ
Alert High Value Setup
WWWWW
Alert Low Value Setup
Operation in case Y=1:
a)
When the captured analog value is higher or lower than the alert values, alarm is
triggered.
b)
SMS or Dial Phone etc corresponding actions described on next page will be taken.
c)
Relay is turn on, and off after preset time lapse.
d)
Alarm will only be re-triggered when the captured analog value returns to normal
range and then reaches beyond the alert values again.
Operation in case Y=4:
a)
When the captured analog value is higher or lower than the alert values, alarm is
triggered.
b)
SMS or Dial Phone etc corresponding actions described on next page will be taken.
c)
Relay is turn on, and only off when analog value is back within Alert Range.
d)
Alarm will only be re-triggered when the captured analog value returns to normal
range and then goes beyond the alert values again.
Application:
•
When temperature is high, ventilation fan is turn on to cool down.
•
When temperature is normal again, ventilation fan is turn off to save power.