7.3.2 Configuration Command Parameters 

Multi-Sensor offers a wide variety of advanced configuration settings. Below parameters can be accessed 
from main controllers configuration interface.

 

Parameter

 

Size

 

Default Value

 

Description

 

10

 

(0x0A)

 

1

 

0x0A

 

Low Battery Power Level of alarm threshold values: 
the value range are 10~50 for percentage, so the 
Battery Low Power level can setting 

10%~50%

.

 

12

 

(0x0c)

 

1

 

0x0A

 

Turn on/off PIR 0x0A indicates the highest 
sensitivity, 0x00 means off PIR detection function.

 

Valid values: 

0x00-0x0A

 

13

 

(0x0d)

 

2

 

0x1e

 

PIR triggers the waiting time value

 

Valid values: 

0x05-0x3BC4

 

14

 

(0x0e)

 

1

 

0x00

 

Whether the BASIC SET command is sent after the 
PIR is triggered

 

0 = Unable 
1 = Enable

 

15

 

(0x0f)

 

1

 

0

 

PIR triggers the correspondence between the value 
of the Basic set and the PIR state, When value is 
0x00 PIR triggers Send the basic set command 0xff 
PIR alarm release send the basic set command 
0x00, otherwise PIR triggers send the basic set 
command 0x00 PIR alarm release send the basic 
set command 0xff.

 

Valid values:0-1

 

100

 

(0x64)

 

1

 

NA

 

Set 101 ~ 104 to default.

 

101

 

(0x65)

 

4

 

0x1C20

 

The interval time of sending the temperature 
reporting. if setting to 

0

 then the 

temperature 

reporting

 is disabled

 

 

1. Valid values: 

0x00-0x28DE80

 

2. The minimum interval time is 1 minutes. For 
example, if the value is set to be more than 1 and 
less than 60, the interval time is 1 minutes, if the 
value is set to be more than 60 and less than 120, 
the interval time is 2 minutes.

 

102

 

(0x66)

 

4

 

0x1C20

 

The interval time of sending the humidity 
reporting. if setting to 

0

 then the 

humidity 

reporting

 is disabled

 

 

1. Valid values: 

0x00-0x28DE80

 

2. The minimum interval time is 1 minutes. For 
example, if the value is set to be more than 1 and 
less than 60, the interval time is 1 minutes, if the 
value is set to be more than 60 and less than 120, 

Содержание 7A-SS-AABC-H0

Страница 1: ...ion 2 2 Product Appearance 2 3 Specification 3 4 Features Capabilities 4 5 Installation Position and Notes 4 6 Product Installation 5 7 Product Usage 6 7 3 1 Association Command 8 7 3 2 Configuration...

Страница 2: ...ation module to connect with Z Wave gateway and this device can be adapted to EU 868 42Mhz or US 908 42MHz If you want your Multi Sensor to be a security device that use secure encrypted message to co...

Страница 3: ...H0 Detection Technology PIR Passive Infrared Detection Angle 110 10 with 2 5m mounting height Detection Distance 5 meters Temperature Accuracy 1 Humidity Accuracy 5 Communication Protocol Z Wave Radio...

Страница 4: ...ON Multi Sensor has detective range 5 meters max The LEEDARSON Multi Sensor Support low battery alarm function The LEEDARSON Multi Sensor Support firmware OTA After installation the direction of detec...

Страница 5: ...Choose the installation location on the wall Rotate universal wheel clockwise and take off it fix the universal wheels by screw or 3M adhesion tape on the wall Take off the battery cover in the back...

Страница 6: ...blink If the inclusion is successful then LED will keep on 2 seconds Otherwise the Multi Sensor will repeat the process from step c automatically Note The Multi Sensor included via SmartStart inclusio...

Страница 7: ...step b Note The Multi Sensor will send Explorer Auto inclusion frame to start Smart Start inclusion When it is removed from a Z Wave network Power On event Please refer to Power On event Short press 3...

Страница 8: ...provisions of Directive 2014 53 EU 7 2 Low voltage alarm to remind changing battery This product has low voltage detection reminder when the battery voltage is in low status the detector will give ou...

Страница 9: ...s 0x00 PIR triggers Send the basic set command 0xff PIR alarm release send the basic set command 0x00 otherwise PIR triggers send the basic set command 0x00 PIR alarm release send the basic set comman...

Страница 10: ...el reporting is disabled 1 Valid values 0x00 0x28DE80 2 The minimum interval time is 1 minutes For example if the value is set to be more than 1 and less than 60 the interval time is 1 minutes if the...

Страница 11: ...cross movement speed is 4m s 0 15m s 6 In order to prevent the PIR sensor s abnormal fault please don t mounting and operating sensor in the bellow conditions Firstly product mounting should prevent i...

Отзывы: