EM522-CAN Field bus Stepper Drive User Manual V1.0
5
3.2.2 CAN Baud Rate Setup
CAN baud rate can be set by DIP switch SW6-SW8, as shown below:
Baud rate(Kbps)
SW6
SW7
SW8
20
on
on
on
50
off
on
on
100
on
off
on
125
off
off
on
250
on
on
off
500
off
on
off
1000
on
off
off
!
Notice
Notes:
(1)
Should restart the power after modifying baud rate.
3.3 LED Light Indication
There are two LED lights for DM56-CAN. The GREEN one is the power indicator which will be always on generally. The
RED one is a protection indicator which will flash 1-2 times in a 3-second period, when protection enabled for a
EM522-CAN. Different number of flashes indicates different protection type ,as shown following table.
Priority
Time(s) of
Blink
Sequence wave of red LED
Description
1st
1
Over-current protection activated when peak
current exceeds the limit.
2nd
2
Over-voltage protection activated when drive
working voltage is greater than 90VDC
3rd
8
EEPROM Fault(need to configure parameter )
4th
12
Operational Amplifier Fault (need to configure
parameter )
!
Notice
Notes:
(1) The protections for detecting
.fault of EEPROM fault and Operational Amplifier need to turn on manually
via configuring parameter, read section 4.4 for detail; (2) When one of the protection is active, the motor shaft will be free
and the red LED blinks. Restart the power to make it function properly after removing above problems.
4. Getting Started
4.1 Wiring Instruction
4.1.1 Power supply & motor cable
Wire diameter: +VDC, GND, A+, A-, B+, B- terminal wire diameter≥0.3mm
2
(AWG15-22)