background image

Maintenance

The Lawler thermostatic water controller, if correctly 

installed and properly used, should require very little 

attention or maintenance. However, every mechanical 

device, including water controllers, deserves some care. 

Strainers should be checked periodically and, if needed, 

cleaned as outlined under “INSPECTING AND CLEANING 

OF VALVE.” To test controller for proper setting and 

operation—proceed as follows:
1.   Place handle in hottest position. Mixing valve should 

deliver water at the temperature stamped on the label.

Standard setting is 110°F. If not 110°F, readjust to 110°F 

according to “TEMPERATURE ADJUSTMENT” procedure in 

another paragraph of this manual.
 

a.   If the temperature is below 110°F and the 

following procedures for adjusting do not increase 

temperature, see paragraph “CHECKING COLD 

WATER SHUT-OFF.”

 

b.   If the temperature is above 110°F and the 

following procedures for adjusting do not decrease 

temperature, see paragraph “CHECKING HOT 

WATER SHUT-OFF.”

Checking Cold Water Shut-Off

1.   Turn adjustment handle to cold position. In this position 

a full flow of cold water should pass through the 

controller.

2.   Shut the hot water stop valve and open cold water 

stop valve. Cold water should flow momentarily until 

thermostat cools and then flow should be reduced to 

a negligible amount with adjustment handle set to the 

warmest position.

Failure to do so will indicate that:
 

a.   Piston is sticking and unit must be cleaned.

 

b.   Spring has lost its strength and should be replaced.

 

c.   On first test, if water does not flow, this can be 

normal if temperature of cold water is below 75°F. 

A quick test is to momentarily turn on hot water so 

the thermostat warms up. If flow then starts, the 

thermostat is good. Failure to obtain flow when first 

starting or when valve is cold is a normal reaction.

Checking Hot Water Shut-Off

1.   With adjustment handle set in hot position, mixing valve 

should deliver water at the temperature stamped on the 

nameplate.

2.   Shut cold water supply to controller. The hot water 

should be reduced to a negligible amount. 

Failure to do so will indicate:
 

a.   Hot water supply isn’t 20°F above the required 

maximum temperature setting.

 

b.   Piston is sticking. Unit must be cleaned.

 

c.   Thermostat has lost charge.

Performance

The Series 67 will maintain outlet temperature to within 

1-1/2°F. under any of the following conditions, providing 

the recommended minimum flow and minimum supply 

temperature differentials are not exceeded:
•  reduction to minimum flow (1 or 1/2 GPM)
•  30°F change in hot water temperature
•  30°F change in cold water temperature
•  50% drop in inlet supply pressure

Maximum Inlet Conditions

Pressure: 125 psig
Temperature: 200°F

Recommended Conditions

Minimum Flow

1 Gallon Per Minute for 67-25 

1/2 Gallon Per Minute for 67-10

Minimum Temperature Differential

Hot and cold water inlets must have a minimum 20°F 

differential from the outlet set temperature.

Three-Way Protection

Three-Way protection is provided with Lawler’s patented 

backseat.
1.   Thermostat Protection. 

Lawler’s exclusive design cuts water flow if the 

thermostat’s liquid motor fails.

2.   Hot Supply Protection. 

Responds automatically if the hot water supply is 

interrupted, or temperature changes.

3.   Cold Supply Protection. 

Guards against scalding if the cold supply is interrupted.

Lawler Thermostatic Valves adjust for changes in both input 

temperature and pressure, maintaining constant output.

Operating Principle

Cold:

 With the stop valves open and adjustment handle in 

the cold position, the plunger is positioned in the liner so 

that the hot ports are closed and the cold ports are open, 

allowing only cold water to pass through the controller.

Warm:

 When the adjustment handle is moved toward the 

warm position, the spring forces the piston upward, opening 

the hot water ports and closing the cold water ports. As 

the warm water flows over the thermostatic element, 

which is solidly filled with a thermo-sensitive liquid, the 

liquid changes in temperature. This change in temperature 

causes an expansion or contraction of the liquid, resulting 

in a movement of the flexible bellows. This movement is 

transferred to the pushrod which in turn moves the piston. 

This moving action proportions the amount of hot and cold 

water allowed to enter the mixing valve in accordance with 

the adjustment handle setting.

Отзывы: