temperedwater.com
5330 East 25th St.
Indianapolis, IN 46218
Phone (317) 261-1212
Fax (317) 261-1208
INSTALLATION &
MAINTENANCE MANUAL
Design and specifications subject to change without notice.
Please refer to
temperedwater.com
to ensure most
current data sheet and other design solutions.
CAUTION: When maintaining and adjusting the
mixing valve, all fixtures should be isolated from
use. Lawler Manufacturing Co., Inc. recommends
that you work safely at all times and in a manner
consistent with the OSHA Lock/Tagout standard,
29 CFR 1910.147 and other applicable standards.
temperedwater.com/patents
M 67 B
ASSE 1017 Approved
ASSE Lead Free Certified
Certified to CSA B125.3
NOTICE!
No mixing valve will work satisfactorily if improperly installed. We suggest, therefore, that you read
these instructions carefully before installing and follow directions as outlined. Handle the mixing valve with care.
The Lawler Series 67 Water Temperature Controller has been carefully assembled and tested at the factory and
set to deliver water at any temperature within the control range stamped on the label. At each inlet of the controller
is a union angle combination stop and check valve with strainer which should be turned open in operation.
Series 67
Combination Thermostatic
and Pressure Balanced
Water Controller
This installation & maintenance manual covers all
configurations of the Series 67.
CAPACITIES – GPM SERIES 67
Pressure Drop PSI
5
10
20
30
45
60
80
Valve Number
Capacity – GPM
67-10
2.5 3.5 5.5 8 10 12 14
67-25
6 10 14 18 25 30 34
1/4 gpm when properly installed in recirculated system.
CAPACITIES – LPM SERIES 67
Pressure Drop PSI
5
10
20
30
45
60
80
Valve Number
Capacity – LPM
67-10
9.4 13.2 22.8 30.3 37.8 45.4 53
67-25
22.7 37.8 53 68 94.6 113 128
Minimum flow for 67-10 is 1/2 Gallon Per Minute
Minimum flow for 67-25 is 1 Gallon Per Minute
DIMENSIONS
Valve Number
A N.P.T.
B N.P.T.
C
67-10
1/2” 1/2” 8”
67-25
3/4”
3/4”
8-3/8”
Dimensions are for reference purposes only. For rough-in dimensions
please refer to Lawler’s Revit/BIM models found at temperedwater.com.
72956_6710_STD_DRW_NODIMS.pdf
B
A
A
C
Содержание 67 Series
Страница 6: ......