- 16 -
Press Menu
Select Key
Press Digit
Select Key
Press Value Select
Key
ConFG
Meter
Configuration
0
00_0
Operation as a rate of
change meter.
Extended meter only.
0
Not rate of change
1
Rate x 0.1
2
Rate x 1
3
Rate x 10
4
Rate x 100
5
Rate x 1000
6
Rate x 10000
0
0
0_0
Operation of front
panel
PEAK
button
and rear connector for
Peak or Valley Display
0
Peak Display. Also selects “Peak” in
“Peak or Valley” at connector above.
1
Valley Display. Also selects “Valley” in
“Peak or Valley” at connector above.
2
Peak (1st push), Valley (2nd push)
3
Front panel Tare
00
0
_0
Auto-tare
0
Meter comes up in normal run mode.
1
Meter comes up in auto-tare mode.
000_
0
Linear or nonlinear
input scaling
0
Linear input
1
Custom curve linearization
Extended meter only.
FiLtr
Filtering
0
0000
Alarm filtering
0
Unfiltered output
1
Filtered output
0
0
000
Peak & Valley filtering
0
Unfiltered Peak & Valley
1
Filtered Peak & Valley
00
0
00
Display filtering
0
Display 16-reading batch average every
17 readings. Updates display 3.5 times/
sec at 60 Hz, 3.0 times/sec at 50 Hz.
1
Display per signal filter setting below.
000
0
0
Adaptive filter
threshold for all filters
0
Low adaptive filter threshold level
1
High adaptive filter threshold level
0000
0
Input signal filter
setting.
Can be applied to dis-
play, setpoint, analog
output, data output.
0
Autofilter. Time constant set by meter.
1
Batch average of 16 readings
2
Moving average, 0.08 sec time constant.
3
Moving average, 0.15 sec time constant
4
Moving average, 0.3 sec time constant.
5
Moving average, 0.6 sec time constant.
6
Moving average, 1.2 sec time constant.
7
Moving average, 2.4 sec time constant.
8
Moving average, 4.8 sec time constant.
9
Moving average, 9.6 sec time constant.
A
Unfiltered. Readings updated at 60/sec
at 60 Hz, 50/sec at 50 Hz.
dEc.Pt
d
.
dddd
Decimal point flashes.
d
.
dddd
dd
.
ddd
ddd
.
dd dddd
.
d
ddddd
.
.
ddddd
Press to shift the decimal point.
Содержание LAUREATE 2 Series