- 18 -
RS232 SERIAL COMMUNICATION
DB9-F
5
3
2
TLU
PC
33
31
30
RS485 SERIAL COMMUNICATION
28 29
28 29
28 29
TLU
TLU
TLU
RS485 +
RS485 -
max 500 m
RS
48
5 +
R
S
48
5 -
RS4
85 +
R
S
48
5 -
RS4
85 +
RS48
5 -
3
2
5
PC R
S
232
RX+
RX-
TX-
TX+
CONVLAU
24 Vcc
+
-
0
TX
RX
VIN
RS485 +
RS485 -
RS485 termination
J2 J1
33
0 VDC
0 VDC
33
0 VDC
33
If the RS485 network exceeds 100 metres in length or baud-rate over 9600 are used,
close the two jumpers, called "RS-485 termination", to activate two 120 ohm
terminating resistors between the ‘+’ and ‘–’ terminals of the line, on the terminal strip
of the furthest instruments.
Should there be different instruments or converters, refer
to the specific manuals to determine whether it is necessary to connect the above-
mentioned resistors.