SERVICE INSTRUCTIONS 

 

Disconnect all sources of power before servicing unit.  If it is 
necessary to replace a factory installed part, be sure to use 
Lattner replacement part. Replacement parts are available 
through authorized Lattner representatives or directly from the 
factory. When ordering replacement parts, always include the 
model and serial numbers. 

 

 
 

LOCATING TROUBLE 

 

 

Problem 
 

 
Possible Cause 

1.  Unit does not operate 

 
Disconnect or control circuit switched off, low water 
condition, high temperature condition, improper setting of 
operating control. 
 

2.  Water temperature too low 

 
Operating control set too low or not operating properly, 
oversized circulator pump, or faulty 
elements/fuses/contactors/wiring. 
 

3.  Water temperature is too 

high 

 
Operating control is set too high or not operating properly, 
undersized circulator pump or not operating properly. 
 

4.  Water temperature correct 

but building is cold 

 
Circulator pump not operating properly, air blocks in piping 
or radiation, control valve in supply or return piping not fully 
open. 
 

5.  Excess pressure causing 

relief valve to open 

 
System head pressure exceeds relief valve setting or 
expansion tank water logged. 
 

 
 
 
 
 
 
 
 

 

 

 

Lattner Boiler Company 

1411 9

th

 St. SW 

Cedar Rapids, IA 52404 

Telephone:  (800) 345-1527 

Fax:  (319) 366-0770 

Web:  www.lattnerboiler.com

 

Содержание SPACE SAVER

Страница 1: ...standby heat source for solar hydronic and water source heat pump systems Vessel ASME Code Section IV H stamped National Board registered rated to 160 psig and 250 degrees Fahrenheit Insulation 4 fiberglass blanket on vessel Elements Incoloy sheathed 75 watts per inch mounted in 150 pound ASA steel flange individually removable Enclosure Ventilated integral control panel constructed of heavy gauge...

Страница 2: ...talled on a level non combustible surface 5 Connect the supply and return piping according to applicable codes Pipe relief valve discharge to nearest floor drain or downward away from any potential hazard to other equipment or personnel 6 Boiler feed connection may be tee d into return connection 7 Electrical knockouts are provided for wiring access All wiring must conform to applicable codes and ...

Страница 3: ...e according to manufacturer s instructions At least once a year boiler elements should be checked 1 Disconnect all power to boiler 2 If a faulty open element is indicated the element may be replaced in the following manner a Isolate boiler from system by closing hand valves in supply and return piping b Drain boiler completely of water c Remove ALL wiring from the elements tagging both the wires a...

Страница 4: ...m damage caused by overheating Automatic Reset High Temperature Cutout s De energizes control circuit in the event of a high temperature condition Control Circuit Lighted Switch De energizes control circuit not main power Operating Controller Maintains water temperature at predetermined setting Pressure Relief Valve Vents pressure to atmosphere in the even of high pressure in excess of relief valv...

Страница 5: ...control 2 Water temperature too low Operating control set too low or not operating properly oversized circulator pump or faulty elements fuses contactors wiring 3 Water temperature is too high Operating control is set too high or not operating properly undersized circulator pump or not operating properly 4 Water temperature correct but building is cold Circulator pump not operating properly air bl...

Страница 6: ...for which the Purchaser may be liable to other persons or damages to property The remedies set forth in this Warranty are exclusive and the liability of Lattner with respect to any contract or sale shall not exceed the cost of repair or replacement of the boiler or other equipment manufactured by Lattner The above Warranty shall not apply to any boiler or other equipment manufactured by Lattner wh...

Страница 7: ...ges in transit and a minimum 15 restocking charge and only if the authorized material is in new and unused condition and returned within one year from original date of shipment The credit will be based on the original invoice price or the current price whichever is lower less the applicable restocking charge SECURITY INTEREST For the purposes of securing payment the Company may issue a lien on the...

Отзывы: