INSTALLATION

UNIT PLACEMENT

Proper unit placement is essential. To ensure safe and effective operation, the location should:

Have enough duct width to mount unit with lamps perpendicular to airflow, within the longest duct length

for increased exposure time.

Be able to support the weight of the unit. If the duct construction does not seem capable of supporting the unit, the

 

duct must be re-enforced, to support the weight, before installing.

Be on the supply air plenum, 

LOCATION A

 (preferred), or on the return air plenum, 

LOCATION B

 (alternative).

Not be mounted under any source of moisture or condensation, such as humidifiers, cooling coils, etc.

Not be mounted near any duct openings, joints, seams, etc. If necessary, seal all openings, joints, seams, etc.

 

using aluminum tape or equivalent ultraviolet resistant material.

Prevent exposure of any plastic, rubber or other non-metallic materials, with inadequate resistance to ultraviolet,

 

such as; plastic drain pans, wiring insulation, flex ducts, humidifiers, filters etc. If necessary, shield all plastic,

 

rubber or other non-metallic materials using aluminum tape, conduit, sheet metal or equivalent ultraviolet resistant

 

material.

Be free of any components that would be damaged by or interfere with the installation.

Be easily accessible and allow enough clearance for routine cleaning or maintenance.

Be downstream from air filters. Dust particles reduce the effectiveness of the unit.

Other mounting positions and locations are possible; contact factory for any questions regarding this.

Larson Electronics, LLC

 

 Phone: (800) 369-6671 

 Fax: (903) 498-3364 

 www.larsonelectronics.com 

5

 of 

10

 

Figure 1 – Unit Placement

Содержание IND-HVAC-DTW-UVC-R1-SS Series

Страница 1: ...ons when packaging equipment to prevent damage Carefully inspect and report all damages Do not install damaged equipment Follow all instructions on any labels or tags Carefully inspect all packing mat...

Страница 2: ...pictorial is used to identify components which must not be disposed of in trash SAFETY INSTRUCTIONS To guard against injury basic safety precautions should be observed including the following 1 Read...

Страница 3: ...harsh environments PRINCIPLE OF OPERATION The design has been carefully conceived to provide adequate germicidal ultraviolet dosage for air stream or surface disinfection in new or existing HVAC Heati...

Страница 4: ...the safety or effectiveness of the installation UNPACKING IN ORDER TO PERFORM THIS TASK BE SURE TO WEAR THE FOLLOWING SAFETY EQUIPMENT SAFETY GLASSES OR A FACE SHIELD AS WELL AS GLOVES Remove the Air...

Страница 5: ...ssary seal all openings joints seams etc using aluminum tape or equivalent ultraviolet resistant material Prevent exposure of any plastic rubber or other non metallic materials with inadequate resista...

Страница 6: ...Outside Duct Mount Opening for outside mount shown Insert unit Attach unit using the face mounting bracket and self drilling screws View inside duct INSTALLATION Larson Electronics LLC Phone 800 369...

Страница 7: ...ly seated 8 Repeat until all lamps have been properly installed 9 Moisten a clean lint free cloth with denatured alcohol and wipe each lamp 10 Clean the outer surface of duct around cutouts 11 Fit the...

Страница 8: ...t our Application Specialists MAINTENANCE Always disconnect power to the unit before performing any service or maintenance WARNING The Air Duct Disinfection Unit is designed to operate with a minimal...

Страница 9: ...censed personnel Table 1 Troubleshooting Problem Possible Cause Corrective Action Unit not operating No electrical power Verify that the unit is connected to a live power source Power connection to fi...

Страница 10: ...ht without adequate eye protection Make it a policy to never enter areas being disinfected with UV lighting systems without powering the system down first Methods of powering down depends on the optio...

Отзывы: