Micro Switch:
The Larkin AFC requires a Fire Suppression System Micro-Switch connection. The Micro-Switch
should be field wired from the Fire Suppression System to the Control Box connecting the Common (C) lead from
the Micro-switch to the Fire Switch Common (FSC) terminal in the Control Box. Connect the Normally Closed
(NC) lead from the Micro-switch to the Fire Switch Normally Closed (FSNC) terminal in the Control Box. Isolate
the Normally Open (NO) lead from the Micro-switch.
WARNING: DO NOT APPLY VOLTAGE THROUGH
MICRO-SWITCH. THIS WILL CAUSE DAMAGE TO THE CONTROL BOARD.
(See micro switch mounting options on page 14)