Remote Switch Panel:
When a remote switch panel is required, field connections must be made from the Light
Switch to terminals Light Switch 1 (LS1) and Light Switch 2 (LS2). Field connections also must be made from the
Fan Switch to terminals Fan Switch 1 (FS1) and Fan Switch 2 (FS2) in the Control Box. Non-lighted switches are
provided for contact closure that will activate the lights and fans.
Hood Sensor(s):
Field-wire low voltage wiring from the hood sensor to the sensor terminals S1 located in the
Control Box (22 AWG Min.). For a system controlling more than one hood, connect the second hood sensor to
terminals S2, the third sensor to terminals S3, and the fourth sensor to terminals S4.
Sensors must be wired
separately
.
The corresponding “Sensor Dip Switch” must be in the ON position for every sensor
connected to the terminal strip
. If a dip switch is in the on position and that sensor is not connected, the system
will be in error and will not operate. If a sensor is connected to the terminal strip and the dip switch for that sensor
is in the off position, the auto activation portion of the system will not function for that sensor.