SLC™ Console Manager User Guide
337
Appendix H: DC Connector Instructions
The -48VDC plug connector is provided to make the input power connectors for your console
server. The -48VDC input source should be circuit breaker or fuse protected at 5 amps.
Input Voltage: -48VDC (acceptable range of -40 to -60 VDC)
Max. Operating Current: 1.5 amps
Max. Input Surge Current: 5 amps
Continuous Power: 100 watts required
Electrically isolated from any source
Connected to reliable Earth ground
The connector kit contains 6 pieces that make 2 complete -48VDC connectors as shown in
.
Figure H-1 Connector Kit Contents
Caution:
Ensure that the SLC power source is turned off while assembling the
connector head.
To assemble the DC plug connectors:
1.
Use 16AWG copper wire to make the connections shown in
Figure H-2 Wire Connections
2.
Strip a suitable amount of wire (~3/8”) from each lead to be inserted into each connector
position.
-48VDC Battery Source
Chassis/Earth Ground
-48VDC Return (RTN)
Insert screwdriver
and press to open.