Show MFR Alarm Conditions
Menu selection:
Menu D1
>Disp. Device : MFR
Press softkey „select“
Menu D2.2
>MFR – Alarm Display
Press softkey „select“
Display
D3.5
„MFR - Alarm Display“ shows up:
Alarms
Signalisation
F = Humidity
M = Motor protection
AC = Operating voltage
T = Compressor runtime
H = Air storage tank pressure too low
DC = Signal voltage
W = Maintenane
N = Cable pressure too low
WT = Door switch open (option)
Fo = Humidity monitoring
0 = no alarm
1 = alarm
0 = off 1 = on
MFR Alarm Display Test
Press softkey „Test“ in display
D3.5
to activate all alarm relays. All alarms
change to „1“ in the ACS display.
At the MFR the alarm LEDs „F“, „H“, „M“, „N“ and „T-Runtime“ as well as the
signal output LEDs „W“, „A“ and „N“ come up.
All alarms must show up in the remote control center.
MFR Alarm Display - deactivate humidity monitoring
Press softkey „F off“ in display
D3.5
to deactivate the humidity monitoring of
the MFR. The signalisation „Fo“ changes to „0“ in the ACS display.
The LED „F-on“ at the MFR goes out.
To reactivate the humidity monitoring immediately press softkey „F off“ for 5
seconds. If the humidity monitoring is not reactivated manually, it will be activat-
ed automatically after a compressor runtime of approximately 2 hours.
MFR – Alarm Display
F – 0 | M - 0 | AC - 1
T – 0 | H - 0 | DC - 1
W – 0 | N - 0 | WT - 0
W – 0 | N - 0
| Fo - 1
______________________
Test |
F off
| back