LANCIER Monitoring ACS 5000 Скачать руководство пользователя страница 15

Page 15

The Lancier Tx Bus

The Lancier Tx bus allows for connection of up to 127 sensors to a pair of mon-
itoring wires. Please note that the ACS can monitor up to 10 parameters that
are transmitted in ten successive time windows, i.e. the ACS uses ten address-
es in the Tx bus. Inasmuch as the measurement values of all sensors connected
to the Tx bus are transferred at separate times, the sensors must be encoded
with a unique address prior to integration.

Encoding

Safety advisory!
Switch off all current in all wires before opening the housing!

• The eight-pin encoding switches (

16

) are located on the lower right side near

the center of the motherboard.  

• To define the ACS address, use the encoding switch (

16/33

) and a narrow

slotted screwdriver (see encoding table).  
Lower switch = 0 = “off”, Upper switch = 1 = “on”

The values of the switch is defined as follows:

Switch 1:

value 1

Switch 2:

value 2

Switch 3:

value 4

Encoding switch (

16/33

)

Switch 4:

value 8

set to “27”

Switch 5:

value 16

Switch 6:

value 32

Switch 7:

value 64

Switch 8:

test switch (should be set to off) 

The lowest address “n” is to be encoded. All other ACS sensors are automati-
cally assigned to the next highest address of the previous sensor in the follow-
ing  sequence:

n

= alarm contact

n+1 = system voltage
n+2 = (most recent) compressor runtime
n+3 = number of compressor operating hours 
n+4 = relative humidity of output air 
n+5 = output air temperature
n+6 = external temperature sensor for ambient air
n+7 = external sensor for compressor temperature
n+8 = external pressure sensor
n+9 = total air flow (flow sensor)

In order to enable readout for the ten Tx bus sensors, the value “n” must not
exceed 117.

Содержание ACS 5000

Страница 1: ...Operating Instructions ACS Addressable Compressor Monitoring Unit Monitors ten physical parameters BA 073157 020 10 14...

Страница 2: ...l Sensors 12 External contact sensor 12 External 20 to 80 C temperature sensor ambient temperature 13 External 50 to 180 C temperature sensor compressor temperature 13 External 0 to 10 bar pressure se...

Страница 3: ...00 Ordering Data Page 3 Operate an MFR with the ACS 22 Read out MFR Values 22 Reset maintenance counter 22 Show MFR Alarm Conditions 23 MFR Alarm Display Test 23 MFR Alarm Display deactivate humidity...

Страница 4: ...System voltage 115 230 V AC voltage 50 V AC 1024 Hz voltage 90 V AC 1792 Hz Address on the Tx bus n 1 n coded address 3 Compressor runtime 0 10 000 s most recent cycle 0 10 000 s 1000 2000 Hz Resolut...

Страница 5: ...lution 0 01 bar 1 Hz Max measuring error at 25 C 2 5 FS Max temperature drift 0 075 FS C Temperature range of the medium 0 90 C Address on the Tx bus n 8 n coded address 10 Flow module ACS 5000 Total...

Страница 6: ...e place of use the recognized technical regulations for safe and professional operation shall also be observed Designated Use The ACS addressable compressor monitoring unit enables assessment of the o...

Страница 7: ...upplied dummy plugs 25 Risk of damage Only the supplied hose connectors are to be used The use of angled or narrow connections could result in false flow readings owing to a nozzle effect Make sure th...

Страница 8: ...ontact is also provided An optional total air flow module and sensors for ambient temperature com pressor temperature and compressor pressure are also available If supplied with an LC display all meas...

Страница 9: ...of an external pressure sensor 10 bar 11 Power line clamp for connection of a compressor power supply monitor 12 Compressor Comp clamp for connection of a compressor runtime monitor 13 Reset button Ho...

Страница 10: ...ll strong enough to support the device The holes should be 148 mm apart horizontally and 88 mm apart vertically Open the housing cover by removing its four screws 3 Mount the device on a wall using th...

Страница 11: ...mage Lead the connecting wire through the supplied screw fittings 24 Tighten down the screw fittings 24 in such a way that a the wire does not move when tugged on and b the wire inlet is sealed Only u...

Страница 12: ...e clamp with the grounding symbol on it 2 Wire Bus A 2 wire bus enables transmission of measurement readings to the monitoring system by the LANCIER Tx bus The wire is to be connected at the a and b c...

Страница 13: ...and o contacts on the Pressure screw clamp 10 System Voltage and Compressor Runtime Allowable diameter per strand inflexible wire 0 2 1 5 mm2 sheathed flexible wire 0 2 0 75 mm2 At least one PE ground...

Страница 14: ...ance 0 05 mm 0 1 mm inner diameter 6 mm PU hose external diameter 8 mm tolerance 0 10 mm 0 1 mm inner diameter 6 mm To dismantle the hose e g for repair work press the gray ring in the connec tor 23 t...

Страница 15: ...a narrow slotted screwdriver see encoding table Lower switch 0 off Upper switch 1 on The values of the switch is defined as follows Switch 1 value 1 Switch 2 value 2 Switch 3 value 4 Encoding switch 1...

Страница 16: ...al of the Testbox Safety advisory Check all transducers before use in order to avoid later malfunction switch in position ON switch in position OFF Code 64 32 16 8 4 2 1 1 2 3 4 5 6 7 8 9 10 11 12 13...

Страница 17: ...e operating voltage Switch on the 20 72 V DC supply voltage of the ACS The ACS starts automatically when the pressurization system is engaged Its display shows up with the screen content last shown fo...

Страница 18: ...des of operation according to the displayed menu In the display B the active menu item is tagged by the marker The marker can be moved up and down by the equivalent softkeys Menu items are selected by...

Страница 19: ...Page 19 Menu Configuration...

Страница 20: ...mpressor runs or is shut down Runtime value sec Last compressor runtime in seconds Operating value h Total operating hours of the equipment Humidity value rh Relative humidity of the output air in Air...

Страница 21: ...he value to set Brightness Brightness of the display value 0 15 Timeout min Period in minutes for shut down of display illumination when dis play is idle value 0 250 Press the softkey select to chose...

Страница 22: ...t compressor run time in seconds Maintenance value h remaining time until next maintenance in hours Operating value h total operating hours of the equipment Reset maintenance counter The maintenance c...

Страница 23: ...ms change to 1 in the ACS display At the MFR the alarm LEDs F H M N and T Runtime as well as the signal output LEDs W A and N come up All alarms must show up in the remote control center MFR Alarm Dis...

Страница 24: ...0 sec after compressor shut down Comp S up value s Opening period of both valves to avoid a compressor start against counter pressure 125 125 sec Runtime max value s Maximum compressor runtime 0 10 00...

Страница 25: ...ngs Menu selection Menu D2 3 back Press softkey select Menu D1 Disp Device ACS Press softkey select Menu D2 1 ACS Settings Press softkey select Display D3 2 ACS Settings shows up The value of the tota...

Страница 26: ...ents of the pres surization equipment Use softkeys A up and down to scroll to the value to set Press softkey select Use softkeys A up and down to increase or to reduce the value Press the softkeys for...

Страница 27: ...key select Menu D2 1 ACS Settings Press softkey select The air flow value must be set accordingly to the mounted flow module Factory setting is already appropriate Display D3 2 ACS Settings shows up U...

Страница 28: ...meets the relevant health and safety requirements of the following EC directives 2006 95 EG Low voltage directive 2004 108 EG Electromagnetic compatibility For proper implementation of the health and...

Отзывы: