4.11 Compressor does not

A. Compressor relay or overload

A. Replace compressor relay or

start (no hum), but

malfunctioning.

overload.

condenser fan motor

B. Inadequate voltage.

B. Measure voltage across common

runs.

and run terminal on compressor.

Voltage must not drop below 90%

of rated voltage.

C. Incorrect wiring.

C. Refer to wiring diagram and correct.

D. Compressor malfunctioning.

D. Replace compressor.

4.12 Compressor starts and

A. Ice bank control failure.

A. Replace ice bank control.

continues to run until

B. Incorrect wiring.

B. Refer to wiring diagram and correct.

freeze up and will not

C. Probe shorted.

C. Check probe for foreign material or

cut off.

damage.

4.13 Compressor does not

A. Inadequate voltage.

A. Measure voltage across common

start but hums.

and run terminal on compressor.

Voltage must not drop below 90%

of rated voltage.

B. Incorrect wiring.

B. Refer to wiring diagram and correct.

C. Starting relay malfunctioning.

C. Replace starting relay. Be sure to

use correct relay. Failure to use

correct relay will cause compressor

failure.

D. Compressor malfunctioning.

D. Replace compressor.

4.14 Compressor starts but

A. Inadequate voltage.

A. Measure voltage across common

does not switch off start

and run terminal on compressor.

winding (will run for only B. Incorrect wiring.

B. Refer to wiring diagram and correct.

a few seconds before

C. Starting relay malfunctioning.

C. Replace starting relay. Be sure to

internal overload

use correct relay. Failure to use

switches compressor off).

correct relay will cause compressor

failure.

4.15 Compressor starts and

A. Dirty condenser.

A. Clean the condenser.

runs a short time but

B. Insufficient or blocked air flow. B. Remove all obstructions and allow

shuts off on overload.

for minimum clearances of 15

inches (380 mm) over top.

C. Inadequate voltage.

C. Measure voltage across common

and run terminal on compressor.

Voltage must not drop below 90%

of rated voltage.

D. Incorrect wiring.

D. Refer to wiring diagram and correct.

E. Defective condenser fan

E. Replace condenser fan motor.

motor.

F. Refrigerant leak.

F. Repair and recharge.

G. Compressor malfunctioning.

G. Replace compressor.

4.16 Compressor and

A. Transformer tripped.

A. Reset transformer.

Condenser Fan Motor

B. Relay will not turn on

B. Failed relay.  Replace Control

will not start after

compressor.

Board.

five (5) minute Power

C. Probe unplugged.

C. Check probe connection at PCB.

Off delay 

(Lancer EIBC

Export only)

.

4.17 Compressor and

A. Improper Wiring.

A. Check Power Indicator Lamp;

Condenser Fan Motor

check wiring per Wiring Diagram.

will not start after

B. Probe unplugged.

B. Check Probe connection at PCB.

five (5) minute Power

C. Damaged electronics.

C. Replace Control.

Off delay

(Lancer EIBC,

USA Only)

.

4.18 Warm drinks.

A. Restricted airflow.

A

Check clearances around sides,

top, and inlet of unit.  Remove

objects blocking airflow through

grill.

B. Dispenser connected to hot

B. Switch to cold water supply.

water supply.

(Section 4.18 continued on next page)

6

TROUBLE

CAUSE

REMEDY

Содержание 500 Series

Страница 1: ...IG 4 22 kg cm2 4 14 BAR CARBON DIOXIDE CO2 REQUIREMENTS Minimum pressure of 70 PSIG 4 92 kg cm2 4 83 BAR Maximum pressure of 80 PSIG 5 62 kg cm2 5 52 BAR ICE BANK WEIGHT 16 pounds 17 26 kg WATER BATH...

Страница 2: ...SSOR STARTS BUT DOES NOT SWITCH OFF START WINDING 6 4 15 COMPRESSOR STARTS AND RUNS A SHORT TIME BUT SHUTS OFF ON OVERLOAD 6 4 16 COMPRESSOR AND CONDENSER FAN MOTOR WILL NOT START AFTER FIVE 5 MINUTE...

Страница 3: ...e top grill A Position dispenser on counter B Remove bonnet from the dispenser C Remove insulation strip from in front of refrigeration deck Fill tank with water until water comes out of overflow tube...

Страница 4: ...s and or brix changes B Remove the bonnet and check the level of water in the water bath Replenish as required and replace the bonnet 2 3 MONTHLY A Unplug the dispenser from power source B Remove the...

Страница 5: ...g lever 3 Wearing sanitary gloves remove drain and air dry the nozzle and diffuser 4 Wearing sanitary gloves replace diffuser and twist nozzle into place 5 Draw drinks to flush the chlorine solution f...

Страница 6: ...ounting block or syrup supply and open shutoffs slightly and check water and syrup flow If no flow check dispenser for freeze up or other problems 4 8 Water only dispensed A Water or syrup shutoff on...

Страница 7: ...starting relay Be sure to internal overload use correct relay Failure to use switches compressor off correct relay will cause compressor failure 4 15 Compressor starts and A Dirty condenser A Clean th...

Страница 8: ...S AND WIRING DIAGRAMS 5 1 500 CED WIRING DIAGRAM 220 240V 50 60HZ LANCER ELECTRONIC ICE BANK CONTROL INTERNATIONAL ONLY TROUBLE CAUSE REMEDY 7 WHEN STARTING UNIT OR IF CURRENT IS INTERRUPTED THERE IS...

Страница 9: ...ANCER ICE BANK CONTROL PROBE RELAY FAN MOTOR COMPRESSOR OVERLOAD C M S L M S LABEL WIRING 500 2500 CED 06 0031 01 WHEN STARTING UNIT OR IF CURRENT IS INTERRUPTED THERE IS A FIVE 5 MINUTE DELAY BEFORE...

Страница 10: ...9 4 1 2 22 6 7 8 16 22 11 21 23 24 10 14 12 13 17 3 27 18 15 22 5 24 25 26 16 15 22 19 20 5 3 CABINET ASSEMBLY 9...

Страница 11: ...Splash Plate Extended No Drip Tray 15 51 0494 01 Support Leg 16 81 0112 Leg Adjustable 17 04 0529 Screw 8 32 x 0 750 18 08 0100 Tubing 19 12 0097 Keylock Switch Optional 20 07 0405 Hole Plug Optional...

Страница 12: ...11 2 4 4 7 3 6 5 29E 29B 29D 29C 29A 23 16 22 17 27 28 20 30A 30B 30C 6 30 18 13 9 4 31 14 31 10C 10A 10D 10B 19 8 1 4 24 29 10 21 12 32 26 25 11 15 33 34 5 4 COMPRESSOR DECK ASSEMBLY...

Страница 13: ...9 03 0028 Retainer Clip Evaporator Coil 20 06 0431 Label 115V 60Hz 1 4 HP 06 0461 Label 230V 50Hz 1 4 HP 06 0744 Label 240V 60Hz 1 4 HP 21 47 0746 02 Low Side Tube 22 04 0237 Screw 8 32 X 250 23 04 00...

Страница 14: ...13 NOTES...

Страница 15: ...2666 e mail daniel freser com cn Freser HK Company Ltd Hong Kong Flat A 24 F Houston Industrial Bldg 32 40 Wang Lung Street Tsuen Wan N T Hong Kong Phone 852 2408 2595 FAX 852 2408 2605 e mail freserh...

Страница 16: ...A4 7ER England Phone 44 1895672667 FAX 44 1895637537 e mail court4lancer msn com Hungary H 2100 G d ll Isaszegi t 67 Hungary Phone 36 28 417 179 FAX 36 28416 881 e mail bodolai compuserve com Lancer A...

Отзывы: