Section 8 - Electrical Connections
Remove wires from the block
by inserting a small flat tip
screwdriver into the top slot.
Push tip all the way down and
push forward. Remove wire.
Main Electrical Installation
1.
All wiring must comply with the National Electrical Code, state and local ordinances, and
be wired by a qualified electrician.
2.
Electrical service MUST be connected to a separate 20 AMP, 115 VAC, 60 HZ single
phase circuit.
Note - A 30 Amp breaker may be necessary depending on heater size, pump selection
and if using the optional compressor (See data label on heater for amperage specific
to your configuration). A qualified electrician should confirm breaker and wire sizes in
accordance with all applicable electrical codes.
3.
Electrical service connections are made in the electrical junction box on the side of the
heater.
4.
The heater must have a safety equipment ground from the main electrical service, strand-
ed 12 GA minimum.
5.
The electrical conductors for electrical service to the heater MUST be stranded 12 GA
minimum.
6.
Install a manual service disconnect near the heater, and label it.
7.
The supply voltage must be maintained at a minimum 110 VAC.
8.
The electrical conductors from the main electrical service must be within approved conduit.
9.
Keep all electrical conductors and conduit away from the chimney connector as well as any
other hot surfaces. Keep the power off until the heater is ready to be started.
WARNING: HAZARD OF ELECTRICAL SHOCK!