35
11
Appendix
1
The product may not be transported, stored or operated outside the specified range. If it is, any guarantees with regard to safety-
related functions lose their validity.
Load
max. 240
Ω
Intrinsic error
±
2
% from 1/3 of the value range
Connection cable
Connection cable
≥
10
m/32.8
ft must be shielded and
applied one side to FPE.
Shunt measuring
Transmission ratio ionisation current to voltage
to be measured
10
mV (DC) = 1
μ
A (DC)
Intrinsic error
≤
2
%
Electrical safety
Contact protection by means of protective impedances
Min. impedance of the connected
measuring device
1
M
Ω
Connection cable
<
1
m/3.3
ft
Output parameters
Technical capacity
Connection cross section
flexible 0.25
...
2.5
mm
2
/24
AWG
...
14
AWG
rapid 0.20
...
2.5
mm
2
/24
AWG
...
14
AWG
Mode
Continuous operation for:
•
Ionisation flame monitoring
Intermittent operation for:
•
Ionisation flame monitoring
•
Optical monitoring
Safety integrity level
DIN EN 61508 Part 2 - SIL 3
Overvoltage category
DIN EN 60730-1, ÜK III
Susceptibility to interference
DIN EN 298
Emitted interference
DIN EN 55022, Class B
Environmental capacity
Protection class
DIN EN 60529, IP20
Ambient temperature
1
-20
°C
…
+60
°C/-4
°F
...
140
°F
Environmental category D according to GL VI Part 7
Relative humidity
3K5, 5
%
...
95
% as per DIN EN 60721-3-3
Vibration and oscillation
GL, VI Part 7, Para. 9, characteristic
1
(0.7g/1.54
lb)
Storage/transport conditions
Storage location
Enclosed spaces
Air temperature
1
-20
°C
…
+80
°C/-4
°F
...
176
°F
Relative humidity
According to DIN EN 60721-3-3:
•
Transport 2K3, up to 95
%
•
Storage 1K3, 5
%
...
95
%
Weight
approx. 0.5
kg/1.1
lb