10
2
General Safety Instructions
2.4
Mounting Notes
NOTICE
Please observe the following warnings to avoid personal injury and damage to property
and the environment:
Compliance with national safety regulations and standards is required at all times.
Note that approvals for accessories, in particular the optical flame sensor, are not part of
the approval of the F130I.
During the assembly and installation process, you must meet the requirements of stand-
ards DIN / VDE 0100, 0550 and DIN / VDE 0722.
Although the device exceeds the requirements of the applicable EMC standards, in some
cases by a considerable amount, proper wiring is the prerequisite for ensuring that the de-
vice and thus the entire plant operates without problems in all cases.
Run the sensor connection cable including its extension physically separate from the
mains and control cables (do not run them parallel to each other).
Avoid running sensor cables near the following components:
- ignition cables
- ignition transformer and electric motors
- contactors resp. switches and frequency transformers, which switch high inductive or
capacitive loads.
Run the supply and signal cables of the flame monitor physically separated from each
other. Take measures to prevent short circuits between the cables.