USER MANUAL

100% 

GEOTHERMAL HEAT

Use the button in the bottom left corner to return to the home screen. Use the arrow button in the bottom right corner to return to previous screen. For 

instructions screen, press the ‘i’ button in the top right corner. In case of operation faults, an alarm button is displayed on the top bar.

3.4.8. Storage tank settings

This shortcut allows accessing the 

Boiler settings 

menu, which will be 

discussed in more detail in the Section on menu functions.

3.4.9. Optional equipment

This shortcut allows accessing the Optional equipment menu, which will 
be discussed in more detail in the section on menu functions.

3.5.  Menu functions

Menu  functions  can  be  accessed  by  pressing  the  menu  button  on  the 
home screen.

3.5.1. Storage tank settings

Storage tank set values are used to adjust the storage tank top and bot-
tom  section  temperature  limits  to  meet  the  site’s  domestic  hot  water 
consumption. The system includes a function that automatically elevates 
storage tank temperature if the heat distribution circuit adjustment curves 
are set higher than the storage tank temperature. Factory settings for the 
storage tank bottom section are 40 °C (min) and 45 °C (max). Factory 
settings for the storage tank top section are 50 °C (min) and 55 °C (max). 

The difference between Min and Max values can be 2...10 °C. The maxi-
mum allowed storage tank top and bottom section temperature set value 
is 60 °C in case of full power geothermal heat pumps and 60 °C (bottom 
section)  /  85  °C  (top  section)  in  case  of  part-power  geothermal  heat 
pumps. In Esi, Emi 22P-Emi 43P or ELi 60P-90P model with separate 
storage  tank  are  the  temperature  sensors  installed  in  the  same  water 
space on the top section of the storage tank. In such case same tempera-
ture settings are used for the top and lower sections of the storage tank.

The value Correction indicates the temperature as corrected by the Timer 
function, Home/Away function, Domestic water boost function, or auto-
matic heat distribution circuit correction.

The storage tank temperature is a decisive factor in compressor starting 
and stopping. The minimum value programs compressor starting at the 
storage tank’s target temperature. The maximum value programs com-
pressor stopping at the storage tank’s target temperature.

The storage tank is heated by the compressor. If the target temperature 
cannot be reached in a certain time (1...24 h), it is presumed that there 
is something wrong with the compressor and the compressor is turned 
off. In such cases, the storage tank is heated by the electric heating ele-
ment. The default set value for this function is 12 h. If the electric heat-
ing element is switched on, the following warning is displayed on the 

Содержание ELI 60-90

Страница 1: ...100 GEOTHERMAL HEAT L MP SS 10 2016 L MP SS GROUND SOURCE HEAT PUMP ESI 6 17 EMI 22 43 ELI 60 90 INSTRUCTIONS FOR USE INSTALLATION AND MAINTENANCE...

Страница 2: ...L mp ss for many decades to come Please familiarize yourself with these instruc tions for use and maintenance Keep the instructions for future use and reference should problems occur These instructio...

Страница 3: ...ce requirements 19 4 2 HVAC installation 19 4 2 1 Heat collection circuit and fill group installation 19 4 2 2 Filling and de aeration of the heat collection circuit 20 4 2 3 Connections between heat...

Страница 4: ...gerant vapour is transferred to COMPRESSOR 2 for ramping up the pressure This is accompanied by steep tempera ture rise In the course of the heat pump process the refrigerant tem perature is the highe...

Страница 5: ...vaporator can commence 2 1 3 Hot water storage tank It is possible to connect multiple storage tanks to ESi EMi ELi models to store the thermal energy created These storage tanks can vary in size L mp...

Страница 6: ...ile final heating takes place inside the coil located at the tank s upper part In general domes tic water temperature must exceed that of the heating water Owing to the two stage heat release of the s...

Страница 7: ...or L mp ss offers multiple solutions for control of the cooling with ss Control control system These are available as accessories The L mp ss product family includes wall and ceiling mounted fan units...

Страница 8: ...unctions 3 4 1 Room temperature adjustment The heat distribution circuit circuits heat curve setting can be adjusted by using the home screen shortcut Room temperature adjustment to achieve room tempe...

Страница 9: ...e away function shortcut can be used to save energy when the residents are away for a long holiday trip for example The function Away changes the heat distribution circuit and storage tank temperature...

Страница 10: ...that time and temperature have been set and the timer function has been activated 3 4 7 Heating curves This shortcut allows accessing the Heating curves menu which will be discussed in more detail in...

Страница 11: ...C min and 55 C max The difference between Min and Max values can be 2 10 C The maxi mum allowed storage tank top and bottom section temperature set value is 60 C in case of full power geothermal heat...

Страница 12: ...essor is seldom on and there is less superheat ing for domestic hot water production In such a case the storage tank upper part and lower part temperatures are close to each other 3 5 2 Heating curves...

Страница 13: ...adjust the brightness of the screen and also the time after the screen goes off 3 5 3 3 Min and max temperature of HD circuits Set values are minimum possible values min and maximum possible values ma...

Страница 14: ...ng circuits where summer function is effecting Circuit can be active during a whole summer when it is controlling bathroom area for example 3 5 3 7 Brine circuit circulation pump control This screen a...

Страница 15: ...hen the cooling system is running In addition the menu will display the current room temperature coolant temperature humidity and dew point value as well as system status heating cooling off External...

Страница 16: ...h the MASTER marking and other devices with SLAVE marking All heat pumps can be monitored and controlled from each heat pumps control screen The compressors rotation extra accessory can be enabled whe...

Страница 17: ...ll of the additional features acquired are displayed on the Optional equipment screen Possible optional equipment includes Optional equipment For more information see Heat distribution circuit 2 Adjus...

Страница 18: ...n platform elements and their fixation screws 4 pc To remove the platform lift the equipment by a fork lift for example 4 1 2 Ground source heat pump installation area We recommend that the L mp ss gr...

Страница 19: ...returning line from the heat collection circuit Esi 1 Lauhduttimelta meno 2 Lauhduttimelle paluu 3 Tulistimelta meno 4 Tulistimelle paluu 5 Maapiiriin meno 6 Maapiirist paluu 1 2 3 4 5 6 1 Flow from...

Страница 20: ...the motor protection switch QM1 on NOTE When using the system s own brine circulation pump for 1 2 4 5 3 de aeration purposes check that the flow direction of the separate submersible pump is always...

Страница 21: ...tion pumps with EMi ELi series determined by demand of the heatable estate Heat circulation pumps will be adjusted according to manufacturer s instructions Grundfos UPM3 AUTO heat circulation pump whi...

Страница 22: ...ctricians are permitted to carry out electrical work on the heat pump according to general regulations GSHP El network Fuse size slow A bivalent models Esi 6 400V 3N 3x10 16 Esi 9 400V 3N 3x16 20 Esi...

Страница 23: ...or NTC X 1 4 and X 1 2 2 X 0 7 mm2 4 3 4 Current monitor If the equipment has been installed in the part power configuration load limiting relays must be installed to the building s master electrical...

Страница 24: ...r fuse The regulator is not au thorised to start the pump Check the measured set values The shut off valves are in the fill position Check that the de aeration and fill valves are in the closed positi...

Страница 25: ...ne off or High pressure switch gone off The low pressure switch has gone off Check functional ity of the brine circuit pump by running it through the mainte nance menu and acknowledge the alarm text d...

Страница 26: ...the page You can see earlier alarms by pressing the alarm history button at the menu functions The software automatically stores the newest 100 fault messages This menu allows resetting the fault log...

Страница 27: ...nput statuses Digital Input ID 1 Compressor 1 Motor protection 10 Low pressure alarm circuit 1 2 Not in use 11 High pressure alarm circuit 1 3 Brine pump 1 Run indicator 12 Compressor 1 Run indicator...

Страница 28: ...ssa alakulmassa olevasta painikkeesta Edelliselle sivulle palataan n yt n oikeassa alakulmassa olevasta nuolipai nikkeesta Oikean yl kulman i painikkeesta avautuu ohjesivu Toimintah iri ss yl palkkiin...

Страница 29: ...setting 50 s If integration time is 10 s the valve position is changed once in every 10 s if required Derivative time 0 10 s Temperature diver gence reaction time Factory setting 0 The longer the der...

Страница 30: ...he soft starter alarms can be activated at this page 5 4 12 Super heat valve control This menu is for adjusting superheat trim valve settings Value in the menu indicates the setting point when compres...

Страница 31: ...ng Three way valve control settings in a free cooling Digital output selection in flexible cooling Manual mode for cooling is intended for testing the function Manual settings can be controlled from t...

Страница 32: ...e voltage fluctuations over 10 of the nominal voltage lightning fire or other respective event Transport dam ages are not covered by the warranty Also the warranty does not cover situations caused by...

Страница 33: ...3 58 13 86 24 Cooling power at temperature 35 C 2 kW 6 91 8 49 10 09 10 24 12 75 12 91 14 37 17 57 23 19 33 15 46 67 67 03 Cooling power at temperature 55 C 2 kW 5 62 6 88 8 16 8 19 10 28 10 32 11 69...

Страница 34: ...nal flow T 4K l s 0 48 0 59 0 70 0 68 0 89 0 83 1 00 1 24 1 64 2 56 900 Maximum external pressure drop kPa 66 65 96 100 84 91 77 208 100 152 750 HEAT DISTRIBUTION CIRCUIT Energy class of HC pump A inv...

Страница 35: ...A A 55 C 35 C 60 dB 00 dB 58 58 58 kW 61 61 61 kW 2015 811 2013 ELi 60 A A A B C D E F G...

Страница 36: ...A A A A A B C D E F G A 2015 811 2013 X ELi 60...

Страница 37: ...ions Colder 157 Warmer 154 Annual energy consumption under colder and warmer climate conditions Colder 36542 kWh a Warmer 20178 kWh a Package information Controller class III Controller contribution t...

Страница 38: ...kW 4 47 COPd Tj 12 C 60 1 kW 4 73 COPd Tj bivalent temperature 58 1 kW 3 08 COPd Tj operation limit 58 1 kW 3 08 COPd Degradiation coefficient when Tj 7 C Cdh 1 00 Bivalent temperatures Heating Averag...

Страница 39: ...A A 55 C 35 C 60 dB 00 dB 58 58 58 kW 61 61 61 kW 2015 811 2013 ELi 60P A A A B C D E F G...

Страница 40: ...A A A A A B C D E F G A 2015 811 2013 X ELi 60P...

Страница 41: ...tions Colder 157 Warmer 154 Annual energy consumption under colder and warmer climate conditions Colder 36542 kWh a Warmer 20178 kWh a Package information Controller class III Controller contribution...

Страница 42: ...kW 4 47 COPd Tj 12 C 60 1 kW 4 73 COPd Tj bivalent temperature 58 1 kW 3 08 COPd Tj operation limit 58 1 kW 3 08 COPd Degradiation coefficient when Tj 7 C Cdh 1 00 Bivalent temperatures Heating Averag...

Страница 43: ......

Страница 44: ......

Страница 45: ......

Страница 46: ......

Страница 47: ......

Страница 48: ......

Страница 49: ......

Страница 50: ......

Страница 51: ......

Страница 52: ......

Страница 53: ......

Страница 54: ......

Страница 55: ......

Страница 56: ......

Страница 57: ......

Страница 58: ......

Страница 59: ......

Страница 60: ......

Страница 61: ......

Страница 62: ...L mp ss is a trademark of Suomen L mp pumpputekniikka Oy We reserve the right to make changes Suomen L mp pumpputekniikka Oy Unikontie 2 62100 Lapua FINLAND www lampoassa com R...

Отзывы: