Weather Sensor u[sonic]WS7 Modbus

(16480) u[sonic]WS7 Modbus

Manual

Modbus data protocols u[sonic]WS7 Modbus

This manual covers the general Modbus specification common to all Modbus sensors from LAMBRECHT meteo. The manual 

allows easy operation of all LAMBRECHT meteo Modbus sensors. Some sensors of the Modbus family offer additional regis

-

ters and functions, which are described in separate documents via the registers and functions described here. The registers 

and functions described in this manual are sufficient for general operation of Modbus sensors in a weather station or PLC.

6.1 General

The Lambrecht meteo Modbus sensors follow the specification of the Modbus organization: “MODBUS APPLICATION PRO

-

TOCOL SPECIFICATION V1.1b3”. 
(See www.modbus.org).

6.2 

Data encoding

MODBUS uses the “Big-Endian” format for addresses and data. This means that if a value is transmitted with a number format 

which is larger than a single byte, that the “most significant byte” is sent first.

Example Big-Endian:
Register size value 16 - bits 
0x1234 is transmitted in the sequence: 0x12 0x34.

To obtain the real measuring value, divide the received register value by the divisor (provided in 6.5, 6.6). 
Values of -9999 indicate an internal sensor error.

6.3 

Standard configuration - default

Baud rate: 

 

19200 Baud

Byte frame according: 

8E1 (1 start bit, 8 data bits, 1 parity bit (even parity), 1 stop bit)

RTU Sensor address: 

13

Default addresses of the LAMBRECHT sensors:

Address

Sensor

1

Wind speed

2

Wind direction

3

Precipitation rain[e]

4

THP

5

EOLOS IND · u[sonic]WS6

6

com[b]

7

PREOS

8

ARCO

9

u[sonic]

10

Pyranometer 2nd Class

11 

Secondary standard Pyranometer

12

PT100 to Modbus converter (temperature)

13

u[sonic]WS7

6.4 

Available Modbus commands

The LAMBRECHT Modbus sensors support the following commands: 
 

• “Read Holding Register” command:  

0x03 (descriptive sensor data registers)

 

• “Read Input Register” command:    

0x04 (measured values registers) 

 

 

 

  

 

(every measured value is to be requested individually)

 

• “Write Multiple Register” command:  

0x10 (Write to configuration registers)

7

Содержание meteo WS6

Страница 1: ...n and display of the measured values using the MeteoWare CS evaluation software Easy space saving mounting on 50 mm standard pipe The Perfect Weather Sensor For industrial use as well as under extreme...

Страница 2: ...the appropriate disposal of waste electronic equipment Content 1 Introduction 3 1 1 Warranty 3 2 Setting to work 3 2 1 Installation conditions 3 2 1 1 Generally 3 2 2 Tools and installation aids 4 2...

Страница 3: ...ring elements This heating is particularly effective against ice and snow in all climatic zones The measuring principle allows very low starting values and high repeat accuracy The sensor rapidly can...

Страница 4: ...he two grup screws Finally the earth screw has to be connected to the ship s ground Acid free contact grease is recommended to protect contact surfaces against corrosion Note Follow all safety instruc...

Страница 5: ...t safety regulations for such works During the electrical installation and termination works the external circuit breaker must be switched off It is not permitted to open those housings by unauthorize...

Страница 6: ...ilization and communication of it s contents prohibited unless definitely permitted Infringement is bound to compensation All rights reserved for patent or registered pattern Ma e ohne Toleranzangabe...

Страница 7: ...r than a single byte that the most significant byte is sent first Example Big Endian Register size value 16 bits 0x1234 is transmitted in the sequence 0x12 0x34 To obtain the real measuring value divi...

Страница 8: ...10 1 Read only 30003 Wind speed maximum m s 10 1 Read only 30004 Wind speed minimum m s 10 1 Read only 30202 Wind direction average 10 1 Read only 30203 Wind direction maximum 10 1 Read only 30204 Wi...

Страница 9: ...n Read Input Register 4 Func Desk Byte count 2 Data 00 14 Checksum OK 3FB9 6 7 Descriptive sensor parameter registers Holding Register Register Parameter name Quantity of registers Remark Access type...

Страница 10: ...2 00 01 61 88 0D 10 9C 41 00 01 7F 41 LEN 9 Transmission Query Source Master Dest Slave 13 Function Write Multiple Register 16 Func Desk Address 40001 Quantity 1 Byte count 2 Register values 00 01 Che...

Страница 11: ...elter 0 1 r h at 10 40 C 3 Shelter inaccuracy 4 r h dependant on v 2 m s and solar radiation 7 Technical data 16480 Weather Sensor u sonic WS7 Modbus Id No 00 16480 001130 Range of application 40 70 C...

Отзывы: