6.8 

Sensor parameters / configuration-parameters

Register

Parameter name 

Allowed values

Quantity of registers

Access type

40001 

Modbus device address 

1

Write only

40200 

Baud rate 

96 = 9600

192 = 19200
384 = 38400

1

Write only

40201 

Parity

1 = even

0 = none

1

Write only

The device must be restarted after each change of a setting!

Example:

 Change the RTU address from 13 to 1

0D 10 9C 41 00 01 02

00 01

61 88 0D 10 9C 41 00

01 7F 41

LEN 

9

Transmission 

Query =>

Source 

Master

Dest 

Slave 13

Function 

Write Multiple Register (16)

Func Desk 

Address=40001, Quantity=1

Byte count 

2

Register values 

00 01

Checksum 

OK:8861

LEN 

6

Transmission 

Response <=

Source 

Slave 13

Dest 

Master

Function 

Write Multiple Register (16)

Func Desk 

Address=40001, Quantity=1

Checksum 

OK:417F

6.9 

Autoconfiguration

All Lambrecht Modbus sensors offer the experienced user the possibility to implement an auto-configuration in his Modbus 

master based on additional information stored in the sensor. 

The necessary information can be found in the document “Lambrecht_Modbus_Autoconfiguration”. 

10

Содержание meteo WS6

Страница 1: ...n and display of the measured values using the MeteoWare CS evaluation software Easy space saving mounting on 50 mm standard pipe The Perfect Weather Sensor For industrial use as well as under extreme...

Страница 2: ...the appropriate disposal of waste electronic equipment Content 1 Introduction 3 1 1 Warranty 3 2 Setting to work 3 2 1 Installation conditions 3 2 1 1 Generally 3 2 2 Tools and installation aids 4 2...

Страница 3: ...ring elements This heating is particularly effective against ice and snow in all climatic zones The measuring principle allows very low starting values and high repeat accuracy The sensor rapidly can...

Страница 4: ...he two grup screws Finally the earth screw has to be connected to the ship s ground Acid free contact grease is recommended to protect contact surfaces against corrosion Note Follow all safety instruc...

Страница 5: ...t safety regulations for such works During the electrical installation and termination works the external circuit breaker must be switched off It is not permitted to open those housings by unauthorize...

Страница 6: ...ilization and communication of it s contents prohibited unless definitely permitted Infringement is bound to compensation All rights reserved for patent or registered pattern Ma e ohne Toleranzangabe...

Страница 7: ...r than a single byte that the most significant byte is sent first Example Big Endian Register size value 16 bits 0x1234 is transmitted in the sequence 0x12 0x34 To obtain the real measuring value divi...

Страница 8: ...10 1 Read only 30003 Wind speed maximum m s 10 1 Read only 30004 Wind speed minimum m s 10 1 Read only 30202 Wind direction average 10 1 Read only 30203 Wind direction maximum 10 1 Read only 30204 Wi...

Страница 9: ...n Read Input Register 4 Func Desk Byte count 2 Data 00 14 Checksum OK 3FB9 6 7 Descriptive sensor parameter registers Holding Register Register Parameter name Quantity of registers Remark Access type...

Страница 10: ...2 00 01 61 88 0D 10 9C 41 00 01 7F 41 LEN 9 Transmission Query Source Master Dest Slave 13 Function Write Multiple Register 16 Func Desk Address 40001 Quantity 1 Byte count 2 Register values 00 01 Che...

Страница 11: ...elter 0 1 r h at 10 40 C 3 Shelter inaccuracy 4 r h dependant on v 2 m s and solar radiation 7 Technical data 16480 Weather Sensor u sonic WS7 Modbus Id No 00 16480 001130 Range of application 40 70 C...

Отзывы: