Продажа, ремонт, сервис и запчасти котлов и горелок Lamborghini
Москва,ул.НародногоОполченив,д. 34,стр.3 (499) 519-03-79, моб. (903) 615-82-73 [email protected]
CALORECL/M A
Electrodes positioning
Two electrodes are envisioned for ignition and one for flame control: these must not touch the deflector or other
metal parts for any reason as they would loose their function, compromising burner functioning.
It is good practice to check the correct position after every intervention on the head.
NATURAL GAS
19
Air servo-motor regulation
The air damper is activated by an electric servo-control. The positions of the damper are determined via the cams,
with reference to the scale on the relevant disc.
The cams are manoeuvred by means of the supplied spanner: they are clutched and self-locked.
The air damper servo-motor must be of the type indicated below.( Servo-motor in the figure in total closure sta
tus)
IV
- /
CAM 1
CAM 2
CAM 3
CAM 4
6
6
6
6
6
6
0
3
2
4
6
9
7
CAM 1 Maximum flame regulation (burner maximum flow rate)
CAM 2 Closure position regulation (value 0)
CAM 3 Minimum flame regulation (burner minimum flow rate)
CAM 4 Not used
GB