35
Alarms such as Low Temperature
Δ
and High Temperature
Δ
can be set in the Setting Menu Each
Alarm can be turned ON or OFF as required and the value can be changed by clicking on the number.
Low temp delta
This alarm is to alert the customer if the coolant supply temperature
doesn’t come within this specified
deltaT from below the set point in a set amount of time. This alarm is disabled by default. If the
customer enables this alarm, then the default value of delta T is 1 and default time is 30 minutes.
Figure 29: Low Temperature Delta
High temp delta
This alarm is to alert the customer if the coolant supply temperature does not come within this
specified deltaT from above the set point in a set amount of time. This alarm is disabled by default. If
the customer enables this alarm, then the default value of delta T is 1 and default time is 30 minutes.
Figure 30: High Temperature Delta